Series 500 nim primitive descriptions (continued) – Siemens 500 NIM User Manual
Page 107
![background image](/manuals/135531/107/background.png)
NIM Primitives
4-54
SIMATIC TIWAY I Series 500 NIM User Manual
Series 500 NIM Primitive Descriptions (continued)
Download Request Parameter Descriptions
The basic format of the download request is as follows:
LLLL 59 XX ...
LLLL 59 00 RRRR MMMM OOOO (may have ASCII format)
LLLL 59 01 RRRR YYYY WW ZZ DD ... DD
LLLL 59 02 RRRR
LLLL 59 03 RRRR
where:
Symbol
Value
Definition
XX
00
Initial download request
01
Download next block
02
Exit download
03
Abort download operation
YYYY
(number)
Requested block sequence number starting with block 0.
RRRR
(number)
Host defined reference field returned with the response.
WW
00
Binary data
01
ASCII data
ZZ
(number)
Segment number corresponding to the segment contained
in the data field.
DD
(number)
Data byte
MMMM
bit map
Upload segment configuration that is present only when
XX = 0. A value of 1 means that the segment is included
in the upload.
OOOO
(number)
Time-out value in seconds (all zeros denote the default
value of two minutes)