Series 500 nim primitive descriptions (continued) – Siemens 500 NIM User Manual

Page 107

Advertising
background image

NIM Primitives

4-54

SIMATIC TIWAY I Series 500 NIM User Manual

Series 500 NIM Primitive Descriptions (continued)

Download Request Parameter Descriptions

The basic format of the download request is as follows:

LLLL 59 XX ...

LLLL 59 00 RRRR MMMM OOOO (may have ASCII format)
LLLL 59 01 RRRR YYYY WW ZZ DD ... DD
LLLL 59 02 RRRR
LLLL 59 03 RRRR

where:

Symbol

Value

Definition

XX

00

Initial download request

01

Download next block

02

Exit download

03

Abort download operation

YYYY

(number)

Requested block sequence number starting with block 0.

RRRR

(number)

Host defined reference field returned with the response.

WW

00

Binary data

01

ASCII data

ZZ

(number)

Segment number corresponding to the segment contained
in the data field.

DD

(number)

Data byte

MMMM

bit map

Upload segment configuration that is present only when
XX = 0. A value of 1 means that the segment is included
in the upload.

OOOO

(number)

Time-out value in seconds (all zeros denote the default
value of two minutes)

Advertising