NIM Primitives

4-18

SIMATIC TIWAY I Series 500 NIM User Manual

Data Element Types and Formats (continued)

TT = B, C = B: Discrete force, 1 byte C: CR force, 1 byte

1

2

3

4

5

6

7

8

MSB

LSB

Y

0

0

0

0

0

0

X

X value

Bit definition

0

Off

On

1

Y value

Force state

0

Unforced

Forced

1

Figure 4-7

Forced Discrete and CR Data Element Format

TT = 17 = Secondary System Status (2 words)*

Word #1:

Each bit set to 1 indicates that the corresponding bit

in word 2 is a reported status.

Word #2:

Status bits
A = 0 NIM in REMOTE mode

= 1 NIM in LOCAL mode
B = 0 P/C System in REMOTE mode

= 1 P/C System in LOCAL mode
C - P undefined (default to 0)

*This is a readĆonly data type

ABCD

MSB

LSB

EFGH IJKL MNOP

ABCDEFGH IJKL MNOP

Figure 4-8

Secondary System Status Data Element Format

Advertising