background image

NIM Primitives

4-25

SIMATIC TIWAY I Series 500 NIM User Manual

Table 4-5

Data Element Address Ranges

P/C Type

Data Type

520–
1101

530–
1102

530–
1104

530–
1108

520C

–1101

520C

–1102

530C

–1104

530C

–1108

530C

–1112

560–
1101

565–
1101

NOTE

L Instruction

TT = 00

1024

2048

4095

8191

*

1024

2048

4096

8192

12000

8192

8192

B

V Variable

TT = 01

512

1024

1024

2048

512

1024

2048

4096

5120

2048

2048

B

K Constant

TT = 02

0

0

0

0

0

0

0

0

0

0

0

A,B

Discrete I/O

X,Y,X&Y Packed

TT = 3,4,6,7

128

1023

1023

1023

1023

1023

1023

1023

1023

2048

2048

B

Control Register

CR, CR Packed

TT = 5,8

256

511

511

511

255

511

511

511

1023

2048

2048

B

Word I/O

WX, WY

TT = 9,A

128

1023

1023

1023

1023

1023

1023

1023

1023

2048

2048

B

Discrete Force

TT = 0B

128

1023

1023

1023

1023

1023

1023

1023

1023

2048

2048

B

CR Force

TT = 0C

256

511

511

511

255

511

511

511

1023

2048

2048

B

Word Force

TT = 0D

128

1023

1023

1023

1023

1023

1023

1023

1023

2048

2048

B

Timer/Counter

TCC/TCP

TT = E,F

128

255

255

255

60

256

256

256

400

1024

1024

B

Drum Step

DSP, DSC, DCP

TT = 10,11,12

10

30

30

30

15

30

30

30

30

128

128

B,D

System Status

TT = 17

1

1

1

1

1

1

1

1

1

1

1

B

Loop Data

TT = 20–35 and

60–75

0

0

0

0

0

0

0

0

0

0

64

A,B

Ramp/Soak Data

TT = 36–3B

0

0

0

0

0

0

0

0

0

0

255

B,C

Analog Alarm

TT = 3C–4A and

7C–8A

0

0

0

0

0

0

0

0

0

0

128

A,B

Notes:
A)

Entry of zero is a non-supported or non-configured Data Type for the P/C.

B)

560 and 565 data sizes are default values for a minimal system configuration. All of these values (except loops, analog
alarms and system status) can be reconfigured.

C)

There are 255 ramp/soak steps for each loop in a 565.

D)

There are 16 steps for each event drum in a P/C.

*

Read only (L-memory in EPROM only).