NIM Primitives

4-31

SIMATIC TIWAY I Series 500 NIM User Manual

Availability: Releases 1.1, 2.1, 2.2, and 3.0

Primitive 02 is the machine status Primitive. It reports the current
operational state of the attached device and NIM in a common format for all
types of attached devices. The NIM gets a status update from the attached
device every 4 seconds (and immediately when an 02 Primitive is issued).

Request: LLLL 02

Response: LLLL 02 HH EE FF, where:

Symbol

Value

Definition

HH

Attached device operational status (mode)

00

Operational and performing instruction data type and
loop execution. (RUN)

01

Operational and performing instruction data type and
loop execution with a non-fatal error detected. (RUN
with non-fatal error)

02

Operational and not performing instruction data type
execution with loop execution. (PROGRAM)

03

Operational and not performing instruction data type
or loop execution. (PROGRAM)

04

Operational and not performing instruction data type
execution with loop execution and a non-fatal error is
detected. (PROGRAM with non-fatal error)

05

Operational and not performing instruction and data
type or loop execution and a non-fatal error is
detected. (PROGRAM with non-fatal error)

80

Not operational due to a fatal error condition.

EE

Attached device auxiliary power source status

00

Auxiliary power source good

01

Auxiliary power source status not available

80

Auxiliary power source not good

FF

NIM operational status

00

Operational

01

Channel A is not functional

02

Channel B is not functional

Status Primitive –