NIM Primitives

4-23

SIMATIC TIWAY I Series 500 NIM User Manual

TT = 46 = Analog Alarm Control Flag (2 words)

MSB

ABCDEFGH

IJKLMNOP RSTUVWXY Zabcdefg

LSB

A

B

C

D

E

F

G

H

-

-

-

-

-

-

-

-
-

-

PV scale 20% offset

Take square root of PV

Monitor HIGH/LOW alarm

Monitor HIGH-HIGH / LOW-LOW alarm

Monitor deviation alarms

Monitor rate-of-change alarm

Monitor broken transmitter alarm

Local setpoint = 0

Remote setpoint = 1

Unused and set to zero

Special function program number

I - X

Y - g

If a bit is set to 1, the corresponding action is enabled.

If a bit is set to 0, the corresponding action is disabled.

Figure 4-15

Analog Alarm Control Flag Data Element Format