NIM Primitives
4-35
SIMATIC TIWAY I Series 500 NIM User Manual
Availability: Release 3.0
Primitive 07, used with the Program Upload and Download Primitives (58
and 59), obtains the attached device segment definition as an ASCII string.
The definitions contain the segment number they represent and relate
one-to-one with the MMMM descriptor (starting at bit P) defined in
Primitive 58. Primarily, this request determines a starting point from which
to obtain the definitions. This allows you to obtain ASCII strings that would
otherwise exceed the maximum returnable length.
Request: LLLL 07 VV SS
Symbol
Value
Definition
VV
Segment type
00
Generic segment definition
01
Secondary device segment definition
02
Program names definition
SS
Starting segment number (or program name) to be
returned
Response: LLLL 07 HH VV KK SS CC DD ... DD
(repeated)
Symbol
Value
Definition
HH
Attached device operational status
VV
Segment type
00
Generic segment definition
01
Secondary device segment definition
02
Program name definition
KK
Total number of segment or program definitions
SS
Segment number definition being returned
CC
Number of bytes in the ASCII DD field
DD
ASCII segment definition defined by the attahced
device. The first two DD descriptors contain the
MMMM (Bit Map) field for the program.
Segment Definition
– Code 07