NIM Primitives

4-35

SIMATIC TIWAY I Series 500 NIM User Manual

Availability: Release 3.0

Primitive 07, used with the Program Upload and Download Primitives (58
and 59), obtains the attached device segment definition as an ASCII string.
The definitions contain the segment number they represent and relate
one-to-one with the MMMM descriptor (starting at bit P) defined in
Primitive 58. Primarily, this request determines a starting point from which
to obtain the definitions. This allows you to obtain ASCII strings that would
otherwise exceed the maximum returnable length.

Request: LLLL 07 VV SS

Symbol

Value

Definition

VV

Segment type

00

Generic segment definition

01

Secondary device segment definition

02

Program names definition

SS

Starting segment number (or program name) to be
returned

Response: LLLL 07 HH VV KK SS CC DD ... DD

(repeated)

Symbol

Value

Definition

HH

Attached device operational status

VV

Segment type

00

Generic segment definition

01

Secondary device segment definition

02

Program name definition

KK

Total number of segment or program definitions

SS

Segment number definition being returned

CC

Number of bytes in the ASCII DD field

DD

ASCII segment definition defined by the attahced
device. The first two DD descriptors contain the
MMMM (Bit Map) field for the program.

Segment Definition
– Code 07