4-19

SIMATIC TIWAY I Series 500 NIM User Manual

Format: TT = 2D = Loop Status (one word)

MSB

A B C D E F G H I J K L M N O P

LSB

A - Loop Mode: If set to one, the loop is in auto mode. If set to zero,

the loop is in manual.
B - Loop Cascade: If set to one, the loop is in closed cascade. If set to

zero, the loop is in open cascade.
C - Error Deviation: If set to one, the loop is in positive error deviation.

If set to zero, the loop is in negative error deviation.
D - PV High High Alarm: If set to one, the process variable is in high

high alarm. If set to zero, the process variable is not in high high

alarm.
E - PV High Alarm: If set to one, the process variable is in high alarm.

If set to zero, the process variable is not in high alarm.
F - PV Low Alarm: If set to one, the process variable is in low alarm.

If set to zero, the process variable is not in low alarm.
G - PV Low Low Alarm: If set to one, the process variable is in low low

alarm. If set to zero, the process variable is not in low low alarm.
H


I


J

K

L

M to P - Spare: Set to zero.

-

-

-

-

-

Yellow Band: If set to one, the loop deviation is in the yellow band.

If set to zero, the loop deviation is not in the yellow band.
Orange Band: If set to one, the loop deviation is in the orange band.

If set to zero, the loop deviation is not in the orange band.
PV Rate of Change Alarm: If set to one, the loop PV is in rate of

change alarm. If set to zero, the loop PV rate of change is not in

alarm (for 560/565 controllers).
PV Broken Transmitter Alarm: If set to one, the loop PV has a

broken transmitter. If set to zero, the loop PV does not have a

broken transmitter (for 560/565 controllers).
Loop Overrun: If set to one, the loop is overrunning its time alloca-

tion. If set to zero, the loop is not overrunning its time allocation (for

560/565 controllers).

Figure 4-9

Loop Status Data Element Format