NIM Primitives

4-22

SIMATIC TIWAY I Series 500 NIM User Manual

Data Element Types and Formats (continued)

TT = 36 = Ramp/Soak Step (13 bytes, IEEE format; TT 76 is IBM format)

000K

TT

SSSSSSSS

RRRRRRRR

K -

Step type (0 = ramp step, 1 = soak step)

TT -

Event status bit data element type (04 = Y, discrete output

EEEE - Event status bit address

SSSS SSSS

- Ramp step: contains the ramp destination setpoint

Soak step: contains the soak time

RRRR RRRR- Ramp step: contains the ramp rateĆofĆchange

Soak step: contains the soak deadband

05 = CR, control relay)

EEEE

Figure 4-13

Ramp/Soak Step Data Element Format

TT = 45 = Analog Alarm Variable Flag (1 word)*

MSB

ABCDEFGH IJKLMNOP

LSB

A - Enable alarm**
B - Disable alarm**
C - Analog variable in high high alarm
D- Analog variable in high alarm
E - Analog variable in low alarm
F - Analog variable in low low alarm
G - Analog variable in yellow deviation alarm
H - Analog variable in orange deviation alarm
I - Analog variable in rateĆofĆchange alarm
J - Analog variable in broken transmitter alarm

K - Analog alarm is overrunning

L - P - Unused and set to zero

* Read only data type
** These bits can accept write updates
If the bit is set to one, the action is enabled.

If the bit is set to zero, the action is disabled.

Figure 4-14

Analog Alarm Variable Flag Data Element Format