Primitive Logical Groups

All Siemens TIWAY Primitives fall into logical groups according to their
function, as shown in Table 4-1. Each Primitive has a request and a
response format. The device initiating the transaction formats a request
Primitive, and the device answering the request formats a response
Primitive. The TIWAY I Primitive subset is taken from the categories listed
in Table 4-1.

Table 4-1

Logical Primitive Assignment

Primitive Code (HEX)

Function

16-Bit Addressing

Extended Addressing

Exception and Status

00 — 0F

80 — 8F

Control

10 — 1F

90 — 9F

Read

20 — 2F

A0 — AF

Write

30 — 3F

B0 — BF

Program Modification
Aids

40 — 4F

C0 — CF

Data Acquisition
Primitives

50 — 6F

D0 —EF

Undefined

70 — 7E

F0 — FE

Expansion

7F

FF