Availability: Releases 1.1, 2.1, 2.2, and 3.0

Primitive 03 allows the Primary to identify the types of devices that exist on
the network. For example, an 03 response from a 520 P/C would be different
from a response from a 5TI P/C.

Request: LLLL 03

Response: LLLL 03 HH DDDD EEEE FFFF GGGG IIII JJJJ KKKK KKKK

Symbol

Value

Definition

HH

Attached device operational status

DDDD

Device type

0000

5TI

0020

520

002C

520C

0030

530

003C

530C

0040

540

0050

550

0060

560

0065

565

007E

UNILINK Host Adapter

0080

PM550

0081

PM551

0100

UNILINK Secondary Adapter

0200

IT–111/121 Intelligent Tank Transmitter

0204

IT–150 Hydrostatic Tank Transmitter

0208

IT–160 Micro Remote Control Unit

EEEE

hex

Instruction data type memory size

FFFF

hex

Variable data type memory size

GGGG

hex

Constant data type memory size

IIII

hex

Local input/output memory size

JJJJ

hex

Global input/output memory size

KKKK

hex

Total memory size (excluding input and output)