Modbus Plus to Ethernet Bridge

6

1.3

Specifications

Table 4 Power

Input

Tolerance

Current

110 V ac (--15% +10%) 47--63 Hz

94--121 V ac

Inrush 15 A at 115 V ac

Operating 1 A nominal

220 V ac (--15% +10%) 47--63 Hz

187--242 V ac

30 A at 230 V ac

Operating 1 A nominal

The bridge automatically senses the power voltage. There is no user--configured

setup other than ensuring the input voltage is within the specified range.

Table 5 Immunity

Parameter

Reference

Component

Limits

Radiated Interference

EN 55011

Enclosure

Class A

Conducted Interference

EN 55011

Enclosure

Class A

Radiated RF Immunity

EN 50140

IEC 1000--4--3

Enclosure

80...1000 MHz, 10 V/m

Radiated RF Impulse

Immunity

EN 50140

Enclosure

900 MHz, 10 V/m

Electrostatic Discharge

IEC 1000--4--2

Enclosure

8 kV air

4 kV contact

Conducted RF Immunity

(Note 1)

EN 50141

IEC 1000--4--6

Network Lines,

Power Lines

0.15...80 MHz, 10 V rms

Fast Transient Burst

IEC 1000--4--4

Network Lines

Power Lines

1 kV Capacitive Clamp

2 kV Direct

Surge Transient

EN 50142

IEC 1000--4--5

Shield to Gnd

Power Lines

2 kV Common Mode

0.5 kV Common Mode,

1 kV Differential Mode

Voltage Dips / Sag

EN 61000--4--11 Power Lines

--30%, 10 ms

--60%, 100 ms

Protective Earth

Continuity

IEC 1131,

par. 4.7.2

Enclosure to

Earth

30 A < 0.1 W

Hipot

Hipot (0...2 km

altitude)

Network Lines

Power Lines

500 v dc

1780 v dc

Notes

1.

For Network Lines longer than 3 m and permanently connected to the

device.