Option 6: node error statistics – Schneider Electric 174 CEV User Manual

Page 73

Advertising
background image

Diagnostic Tools

70

6.13

Option 6: Node Error Statistics

Figure 27 Node Error Statistics

MODBUS PLUS NETWORK STATUS version 2.10
Node Error Counters, Press SPACE to clear.

Adapter:

1

Success: 182
Failure:

0

Information from node 5

(05.00.00.00.00)

0

Pre-transmit deferral error counter

0

Receive buffer DMA overrun error counter

0

Repeated Command received error counter

0

No Try (nonexistent station) error counter

0

Cable A framing error

0

Cable B framing error

0

Receiver CRC error counter

0

Bad packet length error counter

0

Transmit buffer DMA underrun error counter

0

Bad internal packet-length error counter

0

Bad MAC-function-code error counter

0

Communication failed error counter

244

Good receive packet success counter

0

No response received error counter

0

Exception response received error counter

0

Unexpected path error counter

0

Unexpected response error counter

0

Forgotten transaction error counter

This option continuously queries the specified node for a list of its error statistics

and displays the list. As the test runs, the counts in the display can be reset to

zeros by pressing the Space bar.

If you are running the utility on a single-cable network, one of the ‘framing error’

counters will be incrementing continuously due to the open connection on the

monitoring device’s other cable connector. For example, if your single cable is

connected to the Cable A connector, the ‘Cable B framing error’ counter will

increment continuously. In such cases you can disregard the counter.

The option runs continuously and displays a pass count until you terminate it by

pressing Escape.