SPX Cooling Technologies Evaporative Air Cooler FSIG-TS-08A User Manual

Page 11

Advertising
background image

Marley

/

Sigma F Series

Cooling Tower

/

Engineering Data: Environmental

11

Sound Control

Sound produced by a Sigma tower operating in an unobstructed

environment will meet all but the most restrictive noise limita-

tions—and will react favorably to natural attenuation. Where the

tower has been sized to operate within an enclosure, the enclosure

itself will have a damping effect on sound. Sound also declines with

distance—by about 5 dBA each time the distance doubles. Where

noise at a critical point is likely to exceed an acceptable limit, sev-

eral options are available—listed below in ascending order of cost

impact:

• In many cases, noise concerns are limited to nighttime,

when ambient noise levels are lower and neighbors are

trying to sleep. You can usually resolve these situations by

using two-speed motors in either 1800/900 or 1800/1200

RPM configuration—operating the fans at reduced speed

without cycling “after hours”. The natural nighttime reduc-

tion in wet-bulb temperature makes this a very feasible

solution in most areas of the world, but the need to avoid

cycling may cause the cold water temperature to vary signifi-

cantly.

• The Marley Variable Frequency Drive automatically mini-

mizes the tower’s noise level during periods of reduced load

and/or reduced ambient temperature without sacrificing the

system’s ability to maintain a constant cold water tempera-

ture. This is a relatively inexpensive solution, and can pay for

itself quickly in reduced energy costs.

• Where noise is a concern at all times—for example, near a

hospital—the best solution is to oversize the tower so it can

operate continuously at reduced (1200 or 900 RPM) motor

speed. Typical sound reductions are 7 dBA at

2

3

" fan speed

or 10 dBA at

1

2

" fan speed.

• Extreme cases may require inlet and discharge sound attenu-

ator sections—however, the static pressure loss imposed

by attenuators may necessitate an increase in tower size.

This is the least desirable approach because of the signifi-

cant cost impact—and because of the obstruction to normal

maintenance procedures.

Your Marley representative will help you meet your sound

requirements.

Enclosures

Occasionally, cooling towers are located inside architectural

enclosures for aesthetic reasons. Although Sigma towers adapt

well to enclosures, the designer must realize the potential impact

of a poorly arranged enclosure on the tower’s performance and

operation. The designer must take care to provide generous air inlet

paths, and the tower’s fan cylinder discharge height should not be

lower than the elevation of the top of the enclosure. Obtain a copy

of Marley Technical Report #H-004, “External Influences on Cool-

ing Tower Performance” from your Marley sales representative or

on the web at spxcooling.com..

As suggested in the aforementioned Technical Report, it may

also be advisable to specify a design wet-bulb temperature 1°F

higher than normal to compensate for potential recirculation initi-

ated by the enclosure. You’ll benefit from discussing your project

with your Marley representative.

Keeping It Clean

Cooling towers are very effective air washers. Atmospheric

dust able to pass through the relatively small louver openings will

enter the circulating water system. Increased concentrations can

intensify system maintenance by clogging screens and strainers—

and smaller particulates can coat system heat transfer surfaces. In

areas of low flow velocity—such as the cold water basin—sedimen-

tary deposits can provide a breeding ground for bacteria.

In areas prone to dust and sedimentation, you should consider

installing some means for keeping the cold water basin clean.

Typical devices include side stream filters and a variety of filtration

media.

Water Treatment

To control the buildup of dissolved solids resulting from water

evaporation, as well as airborne impurities and biological contami-

nants including Legionella, an effective consistent water treatment

program is required. Simple blowdown may be adequate to control

corrosion and scale, but biological contamination can only be con-

trolled with biocides.

An acceptable water treatment program must be compatible

with the variety of materials incorporated in a cooling tower—ide-

ally the pH of the circulating water should fall between 6.5 and 8.0.

Batch feeding of chemicals directly into the cooling tower is not

a good practice since localized damage to the tower is possible.

Specific startup instructions and additional water quality recom-

mendations can be found in the Sigma User Manual which accom-

panies the tower and also is available from your local Marley sales

representative. For complete water treatment recommendations

and services, contact your local Marley sales representative.

Advertising