Marley

/

Sigma F Series

Cooling Tower

/

Engineering Data : Schematic

4

H

B

TOP OF

FAN CYLINDER

BASE OF

TOWER COLUMNS

FAN DECK

13'-6"

NOTE

1 Use this bulletin for preliminary layouts only. Obtain current

drawings from your Marley representative.

2 All table data is per cell.

3 All tower installations require a minimum of 4'-0" from cen-

terline of tower endwall column to any vertical obstruction at

tower ladder location. Ladder can be located at any corner of

the fan deck. Ladder extends 8

3

8

" below the base of tower

columns on applications with a stainless steel cold water basin.

Ladder stops at top of basin curb wall on applications with a

concrete basin.

Tower installations with an elevation 20'-0" or more from the top

of the fan deck to grade or roof level require a safety cage on

the tower ladder in compliance with OSHA standards. Marley

ladder safety cages are available as an option.

Use this data for preliminary layouts only.
Obtain current drawing from your Marley sales
representative.

The UPDATE web-based selection software
— available at spxcooling.com — provides
Sigma F Series model recommendations based
on customer's specific design requirements.

W

OUT

-T

O-OUT OF T

OWER

A

BAYS AT 4'-0" =

L

C

DIAMETER FAN

3"

3"

COLUMN

COLUMN

CL

CL

COLUMN

CL

Tower

Model

Dimensions

W

L

H

A

B

C

F1211

29'-2"

16'-0"

19'-6"

4

6'-0"

144"

F1221

31'-2"

16'-0"

20'-6"

4

7'-0"

168"

F1231

31'-2"

20'-0"

20'-6"

5

7'-0"

168"

F1241

31'-2"

24'-0"

20'-6"

6

7'-0"

168"

F1251

35'-2"

24'-0"

20'-6"

6

7'-0"

216"

F1261

35'-2"

28'-0"

20'-6"

7

7'-0"

216"

TOWER PLAN

ENDWALL ELAVATION