Specifications

Specification Value

Marley

/

Sigma F Series

Cooling Tower

/

Specifications: Base

18

9.0

Access and Safety:

9.1

Single cell towers shall include a

33" (838 mm) wide by 61" (1.55 m)

high molded FRP access door in one

endwall casing for access to the inte-

rior of the tower. Casing access door

shall be hinged and equipped with a

latch operable from both inside and

outside the tower. Multicell towers

shall have an access door in both

endwalls, and shall include a hinged

door in each transverse partition to

give free access through the tower.

9.2

The top of the tower shall be equipped

with a sturdy 42" (1067 mm) high fiber-

glass guardrail system, complete with

top rails, intermediate rails, and toe-

boards conforming to OSHA standards.

Guardrail posts shall be extensions of

the tower columns.

9.3

One endwall of the tower shall be

equipped with a 20" (508 mm) wide

aluminum vertical ladder, supported

by hot-dip galvanized steel brackets

through-bolted to the endwall struc-

ture. Ladder shall rise from the cold

water basin level to the top of the fan

deck guardrail, and shall be designed

and installed in conformance with

OSHA standards. A horizontal-swing,

gravity-closing safety bar shall be pro-

vided across the ladder opening at the

fan deck.

10.0 Cold Water Basin:

10.1 A large galvanized, rectangular access

door shall be located on both end

panels for entry into the cold water

basin. Rectangular panels are shall be

provided for access to the fan plenum

area to facilitate inspection and allow

maintenance to the fan drive system

10.2 Concrete partitions, if required

between cells in the cold water basin,

shall be installed in accordance with

manufacturer's drawings. Tower

installer shall seal between tower cell

partitions and basin cell partitions.

The access doors on other towers may be unreasonably small.

Specifying the size of the door will cause those bidders to take

exception, alerting you to a potential maintenance headache.

Good maintenance practice requires periodic access to the top of

the tower to inspect the distribution basins, as well as the struc-

tural integrity of the fan deck, fan cylinder, and fan—especially

the fan blade securing hardware. And there are no induced-draft

cooling tower designs that are immune to this need! Please

beware of those manufacturers who suggest otherwise.

For the comfort and safety of your

operating personnel, the Sigma

F Series includes a ladder and

guardrail of the quality and

design indicated—and we

strongly recommend that

you require it of all bidders!

Portable ladders and other

“make-do” access means are

inappropriate for equipment of

this size and complexity.

This basic specification assumes that the tower will be erected

over a concrete basin at grade level. If the tower is to be installed

on an elevated supporting platform, the stainless steel cold water

collection basin indicated on page 20 should be included in the

specifications.