Plan end elevation – SPX Cooling Technologies Evaporative Air Cooler FSIG-TS-08A User Manual

Page 7

Advertising
background image

Marley

/

Sigma F Series

Cooling Tower

/

Engineering Data : Piping Plan 2

7

C

MOTOR

C

F

COLUMN AND

ANCHOR BOLT

TYP. SINGLE CELL

D

TYP. MULTICELL

CL

COLUMN AND

ANCHOR BOLT

CL

INLET

C L

TOWER

AND FAN

C L

FAN

CL

FAN

CL

INLET

CL

INLET

CL

F

FAN TOWER

CL

INLET

CL

MOTOR

CONCRETE

BASIN OPTION

B

DIAMETER

CROSSOVER PIPE

STAINLESS

STEEL BASIN

OPTION

E

FACE OF

A

DIA. GALVANIZED FLANGE

PIPING

LOADS SUPPORTED

BY OTHERS

PIPING

LOADS SUPPORTED

BY TOWER

FLANGE IS

3

/

4

" THICK. BOLT

CIRCLE CONFORMS TO 125 LB.

ANSI SPECIFICATIONS

BASE OF

TOWER COLUMNS

NOTE

1 Use this bulletin for preliminary layouts only. Obtain current

drawings from your Marley representative.

2 Pumping head contributed by the tower is static lift E. Actual

pumping head will vary according to tower circulating GPM.

Total pumping head will be furnished at time of proposal.

3 If your application requires a bypass system, recommended

location is through the tower endwall into the plenum area.

Review of the system by SPX engineering is required.

4 All header and riser piping to be furnished by others.

A corrosion-resistant material or coating for piping is

recommended. All inlet piping loads, including thrust and

seismic, outside of tower plan area must be supported by

others.

Tower

Model

Flow/Cell

GPM

Dimensions

A

B

C

D

E

F

F1210

1050-5750

12"

10"

8'-0"

16'-0"

15'-10

7

8

"

7'-6"

F1220

1050-5750

14"

12"

8'-0"

16'-0"

15'-11

7

8

"

8'-6"

F1230

1320-7200

14"

12"

10'-0"

20'-0"

15'-11

7

8

"

8'-6"

F1240

1500-8650

14"

12"

12'-0"

24'-0"

15'-11

7

8

"

8'-6"

F1250

1500-8650

16"

14"

12'-0"

24'-0"

16'-0

7

8

"

10'-6"

F1260

1850-10100

16"

14"

14'-0"

28'-0"

16'-0

7

8

"

10'-6"

PLAN

END ELEVATION