Specifications: Options

21

Specification Value

and a solid state circuit board for tem-

perature control and low water cutoff.

A control probe shall be located in the

basin to monitor water level and tem-

perature. The system shall be capable

of maintaining 40°F water temperature

at an ambient air temperature of ____

°F. Wiring of the heaters and the heat-

er components shall be the responsibil-

ity of the purchaser.

Convenience and Safety Options

Fiberglass Stairway:

9.3 Replace paragraph 9.3 with the

following: One endwall of the tower

shall be equipped with a structural

fiberglass stairway rising from grade

(roof) to the fan deck. Treads, stringers

and risers shall be molded integrally for

strength and stiffness. Stairs shall be

41.5°, 30" (762 mm) wide, with 8" (203

mm) rise and 9" (229 mm) run. Treads

shall have a nonskid surface. Landings

shall occur at 6'-0" (1.83 m) elevations.

Guardrails shall be 2" tubes, through-

bolted to 3" tube stairway columns.

Stairway foundation shall be by others,

designed in accordance with drawings

provided by the cooling tower manu-

facturer. The stairway shall conform to

OSHA standards.

Wood Stairway:

9.3 Replace paragraph 9.3 with the fol-

lowing: A 30" (762 mm) wide, column

supported, 45° stairway with 8" rise

and run of treated Douglas Fir shall

be provided at the tower endwall ris-

ing from grade (roof) to the fan deck.

Stair columns shall be nominal 4"x4".

Guardrails shall be nominal 2"x4". The

upper guardrail shall have an eased

edge for the protection of operating

personnel. Stairway foundation shall

be by others, designed in accordance

with drawings provided by the cooling

tower manufacturer. The stairway shall

conform to OSHA standards.

Although they are not necessary for routine operation and main-

tenance, stairways do provide a safe and comfortable means of

access to the top of the tower that is often overlooked in the ini-

tial cooling tower purchase. And fiberglass construction provides

long term service and stability. It also is architecturally compat-

ible with the basic tower construction and appearance.

Where atmospheric conditions at the jobsite are not aggressive,

the treated wood stairway may be chosen because of its lower

cost.