Specifications

Marley

/

Sigma F Series

Cooling Tower

/

Specifications: Options

28

Specification Value

Fiberglass Ladder:

9.3 Change paragraph 9.3 to read as

follows: One endwall of the tower

shall be equipped with an 18" (457

mm) wide fiberglass vertical ladder,

supported by hot-dip galvanized steel

brackets through-bolted to the endwall

structure. Ladder shall rise from the

cold water basin level to the top of

the fan deck guardrail, and shall be

designed and installed in conformance

with OSHA standards. A horizontal-

swing, gravity-closing safety bar shall

be provided across the ladder opening

at the fan deck.

Low Noise Tower:

1.1 Add the following at the end of para-

graph 1.1: The cooling tower shall be

quiet operating, and shall produce an

overall level of sound no higher than

____ dBA at the critical location indi-

cated on the Plans.

Fire-Retardant Fiberglass:

3.7 Add the following paragraph in the

Construction section: All fiberglass

components in the cooling tower shall

have a flame spread rating of 25 or

less.

Fan Cylinder Extension:

4.2 Add a third sentence in paragraph

4.2 to read as follows: Overall fan cyl-

inder height shall be 10 feet above the

fan deck level.

Increased Wind and/or Earthquake

Load:

Premium Hardware:

This option is for those customers who either prefer fiberglass

ladders, or whose atmospheric conditions at the cooling tower

location dictate its use.

Sound produced by a Sigma tower operating in an unobstructed

environment will meet all but the most restrictive noise limita-

tions. Where sound levels may be considered critical, however,

low noise levels can be achieved by any of several techniques.

Please discuss your requirements with your local Marley sales

representative.

This option will affect the the standard casing panels, the plenum

partitions between cells, the fan cylinders, and the optional fiber-

glass stairway flights and landing panels.

Extended fan cylinder heights are useful where it is important to

discharge the cooling tower's leaving plume at a certain eleva-

tion. This may be to avoid recirculation, or to keep the plume

above a nearby structure.

If your geographic location dictates the application of higher wind

and/or seismic loads, please discuss with your local Marley repre-

sentative and change paragraph 3.3 to read appropriately. Please

also ask for revised concrete basin or supporting steel drawings

from Marley which reflect the higher load requirements.

Marley can provide hardware materials suitable for all aggres-

sive water conditions, including salt water. Please discuss with

your Marley representative and change specification paragraphs

appropriately.