SPX Cooling Technologies Evaporative Air Cooler FSIG-TS-08A User Manual

Page 27

Advertising
background image

Specifications

Marley

/

Sigma F Series

Cooling Tower

/

Specifications: Options

27

Specification Value

Unless specified otherwise, a Robertshaw or Metrix switch will

be provided. Double-pole, double-throw models are also avail-

able. If purchased in conjunction with

the Control System, it is also factory-

wired. The requirement for manual

reset assures that the tower will be

visited to determine the cause of

excess vibration.

This option is for those customers who either prefer steel lad-

ders, or whose atmospheric conditions at the cooling tower loca-

tion would be detrimental to aluminum.

consist of start and stop control, bypass/

VFD selector switch, Auto/Manual selec-

tor switch, manual speed control, and

solid-state temperature controller. An

emergency bypass selector switch inter-

nal to the panel allowing the fluid cooler

fan motor to be run at full speed shall be

furnished. To prevent heating problems in

the fluid cooler fan motor and to assure

proper gear box lubrication the VFD sys-

tem shall de energize the motor once

25% motor speed is reached and cool-

ing is no longer required. The VFD shall

include de-icing logic with auto canceling

and adjustable time. Speed in De-Ice

mode shall not exceed 50% motor

speed. The fluid cooler manufacturer

shall supply VFD start-up assistance.

Tower vibration testing throughout the

speed range is required to identify and

lockout any natural frequency vibration

levels which may exceed CTI guidelines.

Vibration Limit Switch:

5.5 Add the following paragraph in the

Mechanical Equipment Section: A

single-pole, double-throw vibration

limit switch in the NEMA 4 housing

shall be installed on the mechanical

equipment support for wiring into the

owner's control panel. The purpose of

this switch will be to interrupt power

to the motor in the event of excessive

vibration. It shall be adjustable for sen-

sitivity, and shall require manual reset.

Miscellaneous Options

Galvanized Steel Ladder:

9.3 Change paragraph 9.3 to read as fol-

lows: One endwall of the tower shall

be equipped with an 18" (457 mm)

wide hot-dip galvanized steel vertical

ladder, supported by hot-dip galva-

nized steel brackets through-bolted

to the endwall structure. Ladder shall

rise from the cold water basin level

to the top of the fan deck guardrail,

and shall be designed and installed in

conformance with OSHA standards. A

horizontal-swing, gravity-closing safety

bar shall be provided across the ladder

opening at the fan deck.