Specifications

Marley

/

Sigma F Series

Cooling Tower

/

Specifications: Options

20

Specification Value

Cold Water Basin Options

Stainless Steel Cold Water Basin:

10.1 Replace paragraph 10.1 with the

following: Include a cold water col-

lection basin constructed of 12 gauge

series 304 stainless steel, through-

bolted and sealed to prevent leakage.

A depressed, side outlet sump of

series 304 stainless steel having a

1

4

"

(6.4 mm) thick faceplate drilled for a

standard class 125# ASME flange con-

nection will be included. A removable

stainless steel

1

2

" mesh debris screen

shall cover the top of the sump. An

appropriately sized (4" diameter or larg-

er) stainless steel standpipe overflow

shall be provided. The standpipe shall

be removable for flush-out cleaning of

the basin. A float-operated, mechanical

makeup valve shall also be included,

installed adjacent to the endwall

access door.

Watertight Partition between Tower

Cells with Stainless Steel Cold

Water Basin Option:

10.2 Replace paragraph 10.2 with the

following: Stainless steel watertight

partitions shall be provided between

cells in the cold water basin. They shall

be sealed watertight to the partitions

in the fill and plenum areas of the

tower. Cold water basin partitions shall

have weir openings allowing free flow

of water between cells. Weirs shall be

equipped with bolt-on, gasketed cover

plates to prevent water passage when

required.

Basin Heater:

10.3 Add the following paragraph in the

Cold Water Basin section: Add the

following paragraph in the Cold Water

Basin section: Provide a system of

electric immersion heaters and con-

trols to prevent freezing of water in

the collection basin during periods of

shutdown. The system shall consist

of one or more stainless steel electric

immersion heaters. A NEMA 4 enclo-

sure shall house a magnetic contactor

to energize heaters; a transformer to

provide 24 volt control circuit power;

Marley basins are used to permit the installation of towers on

elevated platforms or foundations.

This is the simplest of several cold water basin designs available

for the Sigma F Series towers. If preferred, a 10 gauge welded

stainless steel basin can be installed.

In addition to the normal partition function of preventing air

bypass (page 14), this option allows you to use each partitioned

cell of your tower independently. This is valuable where a single

multicell tower is serving several separate systems—or where

winter operation may require less than full tower capability.

The basin heater components described at left represent is rec-

ommended for a reliable automatic system for the prevention of

basin freezing.

The ambient air temperature that you fill in should be the lowest

1% level of winter temperature prevalent at site.

Advertising