SPX Cooling Technologies Evaporative Air Cooler FSIG-TS-08A User Manual

Page 12

Advertising
background image

Specifications

Specification Value

Marley

/

Sigma F Series

Cooling Tower

/

Specifications: Base

12

1.0

Base:

1.1

Furnish and install an induced-draft,

crossflow-type, field-erected, structural

fiberglass-framed, PVC film-fill, industrial-

duty cooling tower of _____ cell(s), as

shown on Plans. The limiting overall

dimensions of the tower shall be _____

wide, _____ long, and _____ high to the

top of the fan cylinder. Total operating

horsepower of all fans shall not exceed

____ hp, driven by ___ @ _____ hp

motor(s). Pump head, including static lift

above top of cold water basin curb (or

top of supporting steel), shall not exceed

____ feet of water. Tower shall be simi-

lar and equal in all respects to Marley

Sigma F Series, Model _______.

Your specification base establishes the type, configuration, base

material, and physical limitations of the cooling tower to be

quoted. During the planning and layout stages of your project,

you will have focused your attention on a cooling tower selection

that fits your space allotment, and whose power usage is accept-

able. Limitations on physical size and total operating horsepower

avoid the introduction of unforeseen operational and site-related

influences. Specifying the number of cells, and the maximum fan

hp/cell will work to your advantage.

Your reason for specifying a crossflow type is that crossflow tow-

ers are noted for the accessibility and maintainability of all oper-

ating components. The spacious interior provides easy access

to fill, drift eliminators, all basin accessories—and is one of two

primary accessways to the fan, Geareducer, and other mechani-

cal components.

At the fan deck level, the hot water distribution basins are easily

inspected and cleaned—while the tower is operating, if neces-

sary. The mechanical equipment can also be readily accessed

from this level.

Except for the cold water basin, no counterflow tower component

requiring routine maintenance is as easily accessed. The confined

areas that typify counterflow designs, particularly of forced draft

configuration can make difficult work for maintenance personnel!

Advertising