SEQUENCE OF OPERATIONS 1152 thru 1158

MODEL 1152

NAT.GAS

220 VAC

50 HZ

1 PHASE

MODEL 1153

L.P. GAS

220 VAC

50 HZ

1 PHASE

MODEL 1154

NAT. GAS

240 VAC

50 HZ

1 PHASE

MODEL 1155

L.P. GAS

240 VAC

50 HZ

1 PHASE

MODEL 1156

TOWN.GAS 220/240 VAC

50 HZ

1 PHASE

MODEL 1157

NAT. GAS

220/240 VAC

50 HZ

1 PHASE

MODEL 1158

L.P. GAS

220/240 VAC

50 HZ

1 PHASE

POWER SUPPLY

Electrical power to be supplied to the oven by a three conductor service.

CONTROL BOX AUTO COOL DOWN

When the temperature in the Control Box reaches

120°F ± 3°F (48.9°C ± 1.7°C), the Cooling Fan Thermostat will switch

power to the Control Box Cooling Fans. The Thermostat will interrupt

power to the Cooling Fans when ‘the control box temperature falls to

100°F ± 3°F (37.8°C ± 1.7°C).

MAIN FAN CIRCUIT

Power is permanently supplied to the normally open contacts of the oven

fan relay, the normally open cooling fan thermostat, and to the normally

open oven fan switch. Closing the fan switch supplies line voltage,

through a 1A fuse, to the primary of the power transformer (the trans-

former steps the voltage down to 120 VAC for the control circuit.) 120

VAC is supplied to the cooling fans, terminal #1 of the time delay relay and

to the coil of the oven start relay. These normally open contacts close

enabling the 20 minute time delay relay. The 20 minute time delay relay

supplies 120 VAC to the oven fan relay, its normally open contacts now

close, supplying line voltage to the main fan motor.

BURNER CIRCUIT

Closing the Fan Switch supplies line voltage through the 3 amp fuse, and

oven start relay (closed by activating the Relay in the main fan circuit).

Closing the Burner Switch allows voltage to be supplied through the

normally open gas pressure

switch(located in gas valve and closed

when proper gas pressure is present), through the normally open Air

Pressure Switch (closed by air pressure from main fan), through the

normally closed oven cavity high limit thermostat (opens at 662°F (350°C)

which is manually resetting after a 18°F(10°C) drop), and to the ignition

control.

IGNITION CONTROL

The Ignition Control switches (220 or 240 VAC) to the combustion Blower

Motor, the normally open combustion Air Switch closes upon sensing air

pressure in the burner housing. After a pre-purge period of between 30

and 60 seconds, the Spark Generator is energized, the Main Gas Valve

Solenoid Valve and Burner Pilot Light are energized, and ignition should

now occur.

When the burner ignition occurs, the Flame Sensor must provide micro

amps (normally 2-4 ) to the Ignition Control within 1 second or the burner

system will shut down and the buzzer alarm will sound. To recycle the

burner, switch off the burner switch (this will disable the buzzer), wait 30

seconds, push IN the reset button for the ignition control, and turn on the

Burner Switch. The burner sequence of events should now reoccur.

TEMPERATURE CONTROL

Closing the Fan Switch supplies 120 VAC to the Electronic Temperature

Control. The 2.5K ohm Temperature Potentiometer is

Impinger II - 1100 Series Service Manual - International

9