Troubleshooting & repair, Caution – Lincoln Electric IDEALARC DC 1000 SVM123-A User Manual

Page 46

Advertising
background image

Return to Section TOC

Return to Section TOC

Return to Section TOC

Return to Section TOC

Return to Master TOC

Return to Master TOC

Return to Master TOC

Return to Master TOC

TROUBLESHOOTING & REPAIR

F-6

IDEALARC DC-1000

Observe all Safety Guidelines detailed throughout this manual

If for any reason you do not understand the test procedures or are unable to perform the tests/repairs safely, contact the Lincoln Electric
Service Department for technical troubleshooting assistance before you proceed. Call 216-383-2531 or 1-800-833-9353.

OUTPUT PROBLEMS

PROBLEMS

(SYMPTOMS)

POSSIBLE AREAS OF

MISADJUSTMENT(S)

RECOMMENDED

COURSE OF ACTION

Machine input contactor operates
but machine has no weld output.
Fan runs and pilot light glows.

1. Install a jumper from #2 to #4

on machine terminal strip. If
machine weld output is
restored, the problem is in the
wire feeder or control cable.

2. If remote control is not being

used, make certain the output
control switch (SW3) is in the
“OUTPUT CONTROL AT DC
1000” position.

3. Check 8 AMP fuse in the front

panel. Replace if blown.

4. Check for loose or faulty weld

cable connections.

1. Check operation of output

pilot relay (4CR). There
should be 115 VAC present
on leads #31 and #4 at (4CR)
when #2 and #4 are jumpered
together at the terminal strip.

a. If the correct voltage is pre-

sent and the relay does not
activate, the relay may be
faulty - Replace.

b. If the 115 VAC is missing,

check the associated wiring
for loose or faulty connec-
tions. See wiring diagram.

2. Check the output control

potentiometer (R1) and asso-
ciated circuitry for loose or
faulty connections. See wiring
diagram.

3. Perform

Main Transformer

Test

4. Perform

Firing Board Test.

5. Perform

Control Board Test.

6. Perform

SCR Output Bridge

Test.

CAUTION

F-6

Advertising