LENNOX HEARTH PRODUCTS • ESTATE™ SERIES WOOD-BURNING FIREPLACES • MODELS EST-36, EST-42, EST-50 • INSTALLATION INSTRUCTIONS

Locking Band

Waterproof

Caulk

Roof Ridge

120°

step 8. The standard Security Chimneys

FTF10 roof flashing assemblies include a storm

collar. Slide the storm collar over outer chimney,

rest on flashing spacers and align with top

surface of flashing. Insert tab in slot, pull tight

and bend tab back over slot. Seal storm collar

to outer chimney with roof caulking or mastic

around entire circumference of pipe. Also add

extra roof caulking to the tab/slot area to seal

completely against water penetration (Figure

30). Check all joints very carefully to ensure no

water intrusion can take place.

Figure 31

Figure 29

step 7. Secure flashing by nailing along the

perimeter into roof using 8d nails. If shingled

roof, slide upper end and sides of roof flash-

ing under shingles (trim if necessary), seal the

top and both sides of the flashing to the roof

with roof caulking. Cover nail heads with roof

caulking (Figure 29).

Figure 30

step 9. Security Chimneys locking bands, Model

FLB, may be required if the chimney extends too

high above the roof flashing. As a general rule,

if the chimney extends more than 6' above the

roof flashing, the use of locking bands is advis-

able to strengthen the chimney assembly. Align

the locking band at the chimney joint. Locking

bands wrap around pipe joints equally covering

the joints of both pipe sections.

Use the nut provided and TIGHTEN snugly.

Do not overtighten as this might damage the

chimney section (refer to Figure 30).

step 10. using the ftf10-ctdtm (36" & 42"

models) and ftf13-ctd (50" models) round

termination:

1. Hold termination over top of last chimney

section (Figure 32).

2. Center inner slip section in inner flue pipe-

slip down.

3. Center outer locking section over outer flue

pipe. Push down until locking tabs are firmly

engaged.

4. Pull up slightly on termination to ensure

locking joint has firmly engaged.

Figure 33

Note: It is recommended that all exterior

exposed related metal fireplace components;

such as terminations, flashings, storm collars

and/or flue be painted with a premium-quality,

high-temperature, rust-preventative paint de-

signed for metal. This is especially important

when installations are made in abnormally

adverse or corrosive environments; such as

near lakes, oceans or in areas with consistently

high-humidity conditions. Consult the paint

manufacturers instructions for proper prepara-

tion and application.

For Canadian installations, all chimney installed

outside the building must be galvalume (outer

sections only), effective January 1, 1992. The

appropriate model designations (with a “C”

suffix) are located in the back of this manual.

tEn-foot rulE summary

The minimum chimney height above the roof

and/or to adjacent walls and buildings is speci-

fied by all major building codes.

If the horizontal distance from the peak of

the roof is less then 10' (3 m), the top of the

chimney must be at least 2' (610 mm) above

the peak of the roof.

If the horizontal distance from the chimney

edge to the peak of the roof is more than 10'

(3 m), a chimney height reference point is

established on the roof surface 10' (3 m) hori-

zontally from the chimney edge. The top of the

chimney must be at least 2' (610 mm) above

this reference point. In all cases, the chimney

cannot be less than 3' (914 mm) above the roof

at the edge of the chimney.

The 2' in 10' rule is necessary in the interest

of safety, but does not ensure smoke-free op-

eration. Trees, buildings, adjoining roof lines,

adverse wind conditions, etc., may require a

taller chimney should the fireplace not draft

properly (see Figure 35).

FTF10-CT2RS

Termination

2" (51mm) Min.

Air Space to

Combustibles

Studs

Above

Roof

20"

(508mm)

Note: If chimney extends more than 8' above

roof surface, guy wires are also recommended.

Use three (3) guy wires, attach to locking

band assembly, extend and secure to roof in a

triangular pattern (Figure 31). Guy wires are

not supplied by the manufacturer.

Figure 32

using a ct2 chase termination

Refer to specific installation instruction included

with the CT2 chase termination for clearance

statements and installation details.

(ftf10-ctdtm shown ftf13-ctd similar)