NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

15

LENNOX HEARTH PRODUCTS • ESTATE™ SERIES WOOD-BURNING FIREPLACES • MODELS EST-36, EST-42, EST-50 • INSTALLATION INSTRUCTIONS

multIplE tErmInatIons

If more than one termination is located in the

same chase or within the same general prox-

imity, we suggest they should be separated

in distance at least 24" (610 mm) horizontally

from flue center to flue center and stacked or

staggered vertically at least 18" (457 mm) apart,

from the termination of one smoke exit to the

termination of another smoke exit (Figure 34).

18"

(457mm)

18"

(457mm)

24"

(610mm)

Figure 34

This suggestion is provided in the interest of

better operation. If the terminations are located

too close to each other, smoke may migrate

from one flue into the other.

chImnEy componEnt

calculatIons

The minimum installed height of the completed

fireplace system is 16'0" (4.8 m) for 36" and

42" models and 17'6" for 50" models. The

maximum system height is 80'0" (24.38 m).

To determine the number of chimney sections

and chimney components required, follow

these steps:

Figure 35

3' Min.

(916mm)

Less Than 10' (3m)

2' Min. (610mm) 2' Min. (610mm)

2' Min.

(610mm)

CTDTM

Shown

Note: Both CTD and CTDTM terminations shown for illustration purposes.

Use appropriate termination for the fireplace model installed.

1. Determine total vertical height of the fireplace

installation. This dimension is the distance from

the surface the fireplace sets on to the point where

smoke exits from the termination.

2. Determine the number of chimney compo-

nents required, except chimney sections. This

would include firestop spacers, stabilizers, roof

flashing, etc.

3. The effective heights of the components are

listed below.
fireplace Effective heights

EST-36 & EST-42 = 65-1/4" (1657 mm)
EST-50

= 84" (2134 mm)

pipe Effective heights

FTF10/13-12

= 10-1/4" (260 mm)

FTF10/13-18

= 16-1/4" (413 mm)

FTF10/13-36

= 34-1/4" (870 mm)

termination Effective heights

FTF10-CTDTM

= 10" (254 mm)

FTF10/FTF13-CT2 = 15" - 23"

(381 - 584 mm)

FTF13-CTD

= 4" (102 mm)

FTF13-CTDT

= 12" - 18"

(305 - 457 mm)

FTF13-CT1

= 12" - 18"

(305 - 457 mm)

stabilizer* Effective heights

S4 Stabilizer

= 3" (76 mm)

__________
*Stabilizer is required for every 30' (9.1 m)

of vertical chimney and/or 10' (3.03 m) of

offset chimney.

4. Determine amount of chimney height required

by subtracting total combined height of all pre-

selected components (fireplace and chimney

components from total desired height.)

Reference Vertical Elevation Chart and deter-

mine the number of chimney sections (quantity

and length) required.

spEcIal offsEt InstructIons

To clear any overhead obstructions, you may

offset your chimney system using Security's 30°

offset and return elbows. Use two elbows - an

offset elbow to initiate the offset and a return

elbow to terminate it. A 30° offset elbow, angling

in any direction, may be the first component used

off the top of the fireplace flue collar.

The offset and return elbows may be attached

together, or a section or sections of chimney

may be used between, but must not exceed 20'

(6.1 m) in total length between elbows (Figure

36). If sections of pipe exceed 10' (3 m) between

elbows, a chimney stabilizer must be used at the

midpoint. The stabilizer support straps must be

attached under tension (in shear) to structural

framing members above. When two sets of

elbows are used, the maximum combined length

of chimney used between elbows cannot exceed

20' (6.1 m) (Figure 37). Example: If C

1

= 10' (3

m) then C

2

cannot exceed 10' (3 m).

If an offset exceeds 6' (1.8 m) in length, each

chimney joint beyond the first 6' (1.8 m) of

offset to the return elbow, must be secured by

a No. 8 x 1/2" sheet metal screw located at the

underside of the joint (Figure 38).

A 1/8" (13 mm) diameter hole must be drilled

in the chimney joint using a 1/8" (13 mm)

diameter drill. Hole should be drilled in center

of joint overlap (Figure 39). Be sure to drill

only through the outer chimney casting. Do

not puncture the inner flue.

Maximum offset of chimney system is 30°. Two

offsets must not be assembled to form a 60°

offset. However, two sets of offset and return

elbows may be used on a single flue system,

provided the total height of the system exceeds

22' (6.7 m) (Figure 42).

Return elbow support straps must be securely

attached under tension (in shear) to structural

framing members above. Do not substitute a

FTF10-30 or FTF13-30 offset elbow in place

of a FTF10-E30 or FTF13-ES30 return elbow.