Lennox Hearth WOOD-BURNING FIREPLACES EST-50* User Manual

Page 21

Advertising
background image

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

21

LENNOX HEARTH PRODUCTS • ESTATE™ SERIES WOOD-BURNING FIREPLACES • MODELS EST-36, EST-42, EST-50 • INSTALLATION INSTRUCTIONS

hearth Extensions and Wall shields

A hearth extension must be installed with all

fireplaces. Its purpose is twofold: 1) to protect

a combustible floor in front of the fireplace

from both radiant heat and sparks; and 2) to

distinguish the prescribed hearth extension area

from other unprotected surfaces.

The hearth extension must extend beyond the

front at least 20" (508 mm) and both sides at

least 12" (305 mm) (Figure 47). Use a hearth

extension constructed of a durable noncombus-

tible material having an equal or better (lower k

value) insulating value of k = .84 BTU IN/FT

2

HR

°F or a thermal resistance that equals or exceeds

r = 1.19 HR °F FT

2

/BTU IN. With these values,

determine the minimum thickness/material

required using the formulas shown at right.

When using multiple materials, see the next

page.

note: Any noncombustible material whose k

value is less than .84 or whose r value is more

than 1.19 is acceptable.

If the fireplace is installed on a combustible

floor, use the metal safety strips (provided) on

the floor extending half under the fireplace and

half under the hearth extension.

A wall shield is required where a continuous

perpendicular side wall is within 12" of the

fireplace opening (Figure 48). Use a 36" W

x 36" H wall shield constructed of a durable,

noncombustible material having an equal or

better (lower k value) insulating value than

k = .54 BTU IN/FT

2

HR °F. At no time may a

perpendicular side wall be located closer than

9" from the fireplace opening.

If fireplace is installed diagonally across a 90°

corner; no wall shields are required.

Figure 47

A

B

D

C

C

methods of determining hearth Extension and Wall shield Equivalents

To determine the thickness required for the alternate material, use the “k formula

when the “k” value is known, and use the “r formula” when the “r” value is known.

k

m

= k value per inch of alternate material

r

m

= r value per inch of alternate material

t

m

= minimum thickness required for alternate material

t

s

= standard thickness of the alternate material

k

l

= k value per inch of listed material

r

l

= r value per inch of listed material

t

l

= minimum thickness of listed material

ExamplE: What is the minimum required thickness when using Micore 160 for the

fireplace hearth extension?

NOTE: An asterisk (*) indicates a value taken from Table 1 (next page).

using the “k formula” (when the “k” value is known):

minimum

k-value (per Inch) of

specified min.

thickness of = alternate material (k

m

) x thickness

alternate

k-value (per inch)

of listed

material (t

m

)

of listed material (k

m

)

material (t

l

)

t

m

(inches)

= k

m

x t

l

*.84

t

m

(inches)

= *.35 x 1"

*.84

.416 (inches) = .416

x 1"

ansWEr: The minimum required thickness of the Micore 160 is .417";

therefore, round up to nearest standard thickness available, which is 1/2".

using the “r formula” (when the “r” value is known):

minimum

r-value (per inch)

specified min.

thickness of = of listed material

x thickness

alternate

r-value (per inch)

of listed

material

of alternate material

material

t

m

(inches)

= r

l

x t

l

r

m

t

m

(inches)

= *1.19 x 1"

*2.86

.416 (inches) = .416

x 1"

ansWEr: The minimum required thickness of the Micore 160 is .417";

therefore, round up to nearest standard thickness available, which is 1/2".

models

a

b

c

d

Est-36

20"

(508mm)

36"

(914mm)

12"

(305mm)

60"

(1524mm)

Est-42

20"

(508mm)

42"

(1066mm)

12"

(305mm)

60"

(1524mm)

Est-50

20"

(508mm)

50"

(1270mm)

12"

(305mm)

74"

(1880mm)

Advertising
This manual is related to the following products: