Lennox Hearth WOOD-BURNING FIREPLACES EST-50* User Manual

Page 20

Advertising
background image

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

20

LENNOX HEARTH PRODUCTS • ESTATE™ SERIES WOOD-BURNING FIREPLACES • MODELS EST-36, EST-42, EST-50 • INSTALLATION INSTRUCTIONS

gas lInE connEctIon

The Estate Series fireplaces have been approved

to accept a 1/2" (13 mm) gas line for an ap-

proved gas appliance. Always have the appliance

installed by a qualified, licensed plumber in

accordance with all local building codes. The

gas line may enter either side of the fireplace.

cautIon: plumbIng connEctIons should

only bE pErformEd by a qualIfIEd,

lIcEnsEd plumbEr. maIn gas supply

must bE off WhEn plumbIng gas lInE

to fIrEplacE or pErformIng sErVIcE.

If you’re installing a gas line, connect it before the

fireplace is framed and enclosed in the finished

wall. The gas knockout is determined by a 1-1/8"

(29 mm) round indentation located at the bottom

and slightly off center in the side refractories.

thE KnocKout Is alWays rEmoVEd from

InsIdE thE fIrEplacE. do not rEmoVE thE

KnocKout unlEss you arE InstallIng a

gas lInE. If removal is attempted from the

outer wrapper, side-refractory damage may

occur. With a medium-sized hammer, lightly tap

the surface of the indentation. The refractory

material is very thin in this area and is easily

removed. Once a small hole has been made,

continue tapping until you have reached suffi-

cient diameter for the gas line to fit through. The

entire knockout does not have to be removed.

Remove insulation in the gas line channel.

Install a 1/2" (13 mm) gas supply line through

fireplace wall for connection to a decorative

gas appliance inside the firebox. Outside, the

gas supply line connects to a gas shut-off valve

recessed flush into the wall or floor. The valve

should be controlled by a removable valve key

for safety.

Always plumb gas line installation per local

codes. Check all connections with soap suds;

leaks will bubble. Never test any gas line con-

nection with a match or open flame.

Important: rE-pacK InsulatIon matE-

rIal In squarE holE around gas lInE;

IntErIor and ExtErIor, to sEal.

This provision is intended only for connection

to a decorative gas appliance incorporating an

automatic shut-off device and complying with

the standard for Decorative Gas Appliances for

installation in vented fireplaces, ANSI Z21.60.

Install in accordance with the National Fuel

Gas Code, ANSI Z223.1. This complies with

the revised U.L. 127 standard.

cautIon: WhEn usIng thE dEcoratIVE

gas applIancE, thE fIrEplacE dampEr

must bE sEt In thE fully opEn posItIon.

Vent free appliances

These units have been tested and approved to

ANSI/IAS/AGA Z21.11.2 for use with unvented

gas appliances and complies with the standard

for Factory-Built fireplaces, UL 127.

The unit has been tested for use with any unvented

gas log sets having a maximum rating of 40,000

BTU. The minimum mantel configurations are

outlined in Figures 45 and 46.

These fireplaces have been marked with a

maximum rating of 40,000 BTU to assure that

homeowners do not exceed the allowable limits

for all allowed installations of mantels.

nEVEr Install an unVEntEd gas log sEt

WIth a btu grEatEr than 40,000.

cold clImatE InsulatIon

If you live in a cold climate, it is especially

important to seal all cracks around the fire-

place opening with noncombustible material

and wherever cold air could enter the room.

Surrounding materials must be caulked where

it meets the black metal facing of the fireplace

to avoid cold air intrusion. Use noncombustible

caulking material only on fireplace facing to

seal. Also, the outside air inlet duct should be

wrapped with noncombustible insulation to

minimize the formation of condensation. Do

not place insulation materials against chimney

sections.

Note: A 2" (51 mm) air space must be preserved

for all combustible materials extending for any

continuous length adjacent to the chimney.

It is especially important to insulate between the

studs of an outside chase cavity and under the

floor if the floor is above ground level. Do not

place insulation directly against the fireplace

or chimney system.

fIrEplacE fInIshEs

mantels and trim

In Canada, the minimum height for a combus-

tible mantel is 24" (610 mm) above the fireplace

opening (EST-36 and EST-42 only). Figure 45

shows a typical Canadian installation.

NOTE: The EST-50 is not for use in Canada.
In the U.S., combustible mantels and trim

may be installed as shown in Figure 46 as per

NFPA 211-Mantel/Trim Clearances. If a mantel

is of a noncombustible material, it is exempt

from these requirements, as long as it does

not interfere with the installation or operation

of glass doors.

Combustible

Mantel

Spacer

Noncombustible

Wall Covering

Finished

Wall

Canadian Installation

(36 and 42 models only)

Fireplace

Opening

Facing

Flush

24" Min.

(610mm)

8" Max.

(203mm)

Figure 45

Figure 46

typical canadian Installation

(Est-36 and Est-42 only)

Fireplace

Opening

EST-36 & EST-42:

6-9/16" (167mm)

EST-50:

10" (254mm)

12"

(305mm)

Min.

Combustible

Mantel

and Trim

Spacer

Noncombustible

Wall Covering

Finished

Wall

12"

(305mm)

Max.

1-1/2" (38mm)

FIREPLACE FINISHES:

Mantels and Trim

In installations other than Canada, combustible mantels

and trim may be installed as shown in the illustrations

below and as per NFPA 211-Mantel/Trim Clearances. If a

mantel is of a noncombustible material, it is exempt from

these requirements as long as it does NOT interfere with

the installation or operation of glass doors.
For combustible mantel and trim specifications in

Canadian installations (EST-36 and EST-42 only), see

the fireplace Installation Instructions.

Typical U.S. Installation