Installation and Configuration

13

3. Install the rear member of each bracket assembly

into the rack enclosure with two (2) M5 screws

provided in this kit (see figure at right). The return

flanges on the bracket assembly fit to the inside of

rack mounting rails. Insert screws loosely (finger-

tight) into the top and bottom holes of the return

flange on the rear member. Extend the bracket

assembly by sliding the front member forward until

it touches the front rack mounting rail. Insert two

(2) M5 screws loosely (finger-tight) into the top and

bottom holes of the return flange on each front

member. Make sure that the bracket assemblies

are at the same mounting height on all four (4) rack

mounting rails.

4. Get eight (8) M4 screws and eight (8) M4 nuts from

the hardware pack in this kit. Each nut has a

locking, nylon insert that begins gripping the screw

when it is halfway tight. Make sure to tighten the

nut and screw completely to ensure locking action.

Fasten the rear member and the front member

together using (4) screws and (4) nuts per bracket

assembly as shown in at right. For maximum

support, insert fasteners for each bracket assembly

as far apart as possible, depending on rack depth,

while still joining both members (see figures at

right). Check alignment of bracket assemblies and

TIGHTEN ALL SCREWS FROM Steps 2 and 3.

5. Prepare the UPS or battery cabinet (the

“equipment”) for rack mounting by following

instructions in the equipment’s user manual. The

equipment may require additional parts to be

added or parts to be removed for rack mounting.

After it is prepared, lay the equipment in rack-

mounting position. Fasten the inner members from

Step 1 to the equipment on both sides as shown at

right with seven (7) M4 screws provided in the kit.

Make sure retaining latch is near the rear of the

equipment as shown (see figure below right).

6. Open the grease packet provided in the kit. Apply a

bead of grease 25mm (1") long at four (4) places

inside the bottom, curved tracks of the front

members as shown below right. The grease will

allow the equipment to slide into the bracket

assemblies more easily.

!

6.

CAUTION

Lifting equipment into the rack may be a two-

person job, depending on the weight of the

equipment. Liebert recommends taking the

internal batteries out of the UPS during rack

installation. This will make the UPS cabinet

lighter and easier to handle. The GXT2-

6000RTL630 weighs 151 lb (67kg). For the

battery cabinet’s weight, see the unit’s user

manual.

M5 screws

M5 screws

Front rack

mounting rails

Rear rack

mounting

rails

813mm (32")

rack depth

M4 nuts

M4 nuts

M4

screws

457mm

(18") rack

depth

M4 nuts

M4 nuts

M4

screws

UPS or battery

cabinet

Front

M4 screws

M4 screws

Retaining latch

Advertising