Installation and Configuration

17

5.4.2 Distribution Box Electrical Connections

Electrical connections are made through a removable power distribution box that attaches to the rear

of the UPS.
The installer must provide a 30A branch circuit breaker, with NEMA L6-30R receptacle. The Input

circuit breaker on the distribution box and the Output circuit breaker on the rear fixed-panel of the

UPS disconnect all power between the main cabinet and the distribution box.
Models equipped with a manual bypass switch pass bypass power directly to the bypass switch from

the input power cord. The input circuit breaker on the distribution box does not disconnect power

from the manual bypass switch.

Figure 7

PD-L630 power distribution box electrical connections diagram

Utility

Input

30A External
2-Pole Branch
Circuit Breaker

30

Input

CB

Utility

UPS

Output

UPS

Output

CB

30

UPS - PFC, Battery, Inverter