Table 5 battery run times, Table 5, Battery run times – Liebert GXT2-6000RTL630 User Manual

Page 38

Advertising
background image

Troubleshooting

34

Using the configuration program, the user may specify the number of GXT2-240VBATTUL external

battery cabinets attached to the UPS. The factory default is programmed for internal batteries only.
Table 5 above shows the estimated run times at different loads.

Table 5

Battery run times

Load%

6000VA

Internal Battery

(minutes)

10%

94

20%

46

30%

29

40%

21

50%

17

60%

13

70%

11

80%

9

90%

8

100%

7

Internal Battery

+ 1 External Battery

Cabinet (minutes)

10%

222

20%

124

30%

81

40%

60

50%

49

60%

39

70%

33

80%

28

90%

24

100%

21

Internal Battery

+ 2 External Battery

Cabinets (minutes)

10%

350

20%

197

30%

135

40%

105

50%

85

60%

70

70%

58

80%

50

90%

43

100%

38

Internal Battery

+ 3 External Battery

Cabinets (minutes)

10%

478

20%

269

30%

185

40%

145

50%

123

60%

101

70%

85

80%

73

90%

63

100%

55

Internal Battery

+ 4 External Battery

Cabinets (minutes)

10%

606

20%

341

30%

235

40%

184

50%

156

60%

131

70%

113

80%

97

90%

85

100%

75