0 specifications, Table 6 ups specifications, Pecifications – Liebert GXT2-6000RTL630 User Manual

Page 40: Table 6, Ups specifications, See 13.0 - specifications

Advertising
background image

Specifications

36

13.0 S

PECIFICATIONS

Table 6

UPS specifications

Model Number

GXT2-6000RTL630

Model Rating

6000VA/4200W

Dimensions, in. (mm)

Unit, W x D x H

8.7 x 21.5 x 16.9 (221 x 547 x 430)

Shipping, W x D x H

22.0 x 27.2 x 19.7 (560 x 690 x 500)

Weight, lb (kg)

Unit

57.2 (26)

Shipping

81.5 (37)

Input AC Parameters

Nominal Operating Frequency

50 or 60Hz (Factory Default = 60)

Factory Default VAC

208VAC

User Configurable VAC

208/220/230/240VAC

(May be modified using configuration program)

Operating Voltage Range Without

Battery Operation

176 – 276VAC

Maximum Allowable VAC

276VAC

Input Frequency Without Battery

Operation

40 - 70Hz

Input Power Connection

L6-30P Plug (on PD-L630 power distribution box)

Output AC Parameters

Factory Default VAC

208VAC

Output Connections

(2) L6-20R and (2) L6-30R on 12" (300mm) cords

(on PD-L630 power distribution box)

Frequency

50Hz or 60Hz, Nominal

Waveform

Sinewave

Main Mode

Overload

>200% for 96 milliseconds; 131 - 199% for 2 seconds;

112- 129% for 10 seconds with transfer to bypass

Bypass Protection Limits

Disable Bypass operation

If input voltage exceeds ±15% of the nominal voltage

Re-enable Bypass operation

If input voltage returns to within ±10% of nominal output voltage

Disable Bypass operation

When the input frequency prevents synchronous operation

Environmental

Operating Temperature

32

°F to 104° F (0°C to 40°C)

Storage Temperature

5

°F to 122° F (-15°C to 50°C)

Relative Humidity

0-95% non-condensing

Operating Elevation

Up to 6600 ft (2000m) at 104

°F (40°C) without derating

50,000 ft. (15,000m) maximum

Storage Elevation

Audible Noise

<55 dBA, at 3 ft. (1m) from the rear

<50 dBA, at 3 ft. (1m) from the front or sides

Agency

Safety

UL, C-UL Listed to UL1778

EMI/EMC

FCC Class B

ESD

EN61000-4-2, Level 4, Criteria A

Radiated Susceptibility

EN61000-4-3, Level 3, Criteria A

Electrical Fast Transient

EN61000-4-4, Level 4, Criteria A

Surge Immunity

EN61000-4-5, Level 3, Criteria A

Transportation

ISTA Procedure 1B