Table 9 external battery cabinet specifications, Table 9, External battery cabinet specifications – Liebert GXT2-6000RTL630 User Manual

Page 42

Advertising
background image

Specifications

38

Table 9

External battery cabinet specifications

Model Number

GXT2-240VBATTUL

Used w/ UPS model

GXT2-6000RTL630

Dimensions, W x D x H, in. (mm)

Unit (with bezel)

6.9 x 20.6 x 16.9 (176 x 522 x 430)

Shipping

22.0 x 27.2 x 17.9 (560 x 690 x 455)

Weight, lb (kg)

Unit

145 (65)

Shipping

173.1 (78.5)

Battery Parameters

Type

Valve-regulated, non-spillable, flame retardant, lead acid

Qty x V

20 x 12V

Battery Manufacturer, Part #

Yuasa / REW 45-12

Backup Time

See Table 5 - Battery run times

Environmental

Operating Temp

32

°F to 104°F (0°C to 40°C)

Storage Temp

5

°F to 122° F (-15°C to 50°C)

Relative Humidity

0-95% non-condensing

Operating Elevation

Up to 6600 ft. (2000m) at 104

°F (40°C) without derating

Storage Elevation

50,000 ft. (15,000m) maximum

Agency

Safety

UL, C-UL Listed to UL1778

Transportation

ISTA Procedure 1B

Advertising