Controls and Indicators

21

8.0

C

ONTROLS

AND

I

NDICATORS

8.1

ON/Alarm Silence/Manual Battery Test Button

This button controls output power to connected load(s) and has three functions:

• ON
• Alarm Silence
• Manual Battery Test

ON - Pressing this button will start up the UPS in order to provide conditioned and

protected power.
Alarm Silence - To silence alarms, press this button for at least one Second. After the

alarm is silenced, the GXT2-6000RTL630 will reactivate the alarm system to alert of

additional problems.

Manual Battery Test - To initiate a manual battery test, press the ON button for at least one second

while operating from utility power with no alarm conditions present.

• If only three of the five Battery LEDs illuminate, allow the UPS to recharge the batteries for 24

hours.

• After 24 hours, retest the batteries.
• After the batteries have been retested, if only three of the five Battery LEDs illuminate, contact

your local dealer, Liebert representative or Liebert Worldwide Support Group.

8.2

Standby/Manual Bypass Button

This button controls output power to connected load(s) and has dual functions:

Standby and Manual Bypass.

NOTE
The LOW BATTERY and BYPASS reminder alarms CANNOT be silenced.

!

CAUTION

Pressing the Standby/Manual Bypass button once will transfer the

load to bypass power. Pressing the Standby/Manual Bypass button a

second time within 4 seconds will cut off power to the output

receptacles and connected loads. Perform all necessary shutdown

procedures on connected loads before pressing this button twice.

UPStation GXT

BATTERY

UPS ON

BYPASS

AC INPUT

All indicators illuminated

for illustration only.