1 attach power distribution box, Figure 6 pd-l630 power distribution box, Attach power distribution box – Liebert GXT2-6000RTL630 User Manual

Page 20: Figure 6, Pd-l630 power distribution box, Installation and configuration 16

Advertising
background image

Installation and Configuration

16

5.4.1 Attach Power Distribution Box

Whenever the power distribution box is not attached to the UPS, the cover must be slid over the elec-

trical connections to prevent damage or injury.
To attach the PD-L630 power distribution box to the UPS:
1. Loosen the white cover over the electrical connections by backing out the three screws securing

the cover one turn each.

2. Slide the cover open to expose the electrical connectors.
3. Gently retighten the three screws loosened in Step 1.
4. Align the connectors on the box and UPS.
5. Push the box into place.
6. Holding the box firmly against the UPS, tighten the three captive mounting screws until the box

is secure. Do not overtighten.

Figure 6

PD-L630 power distribution box

OUTPUT
BREAKER

20A 240V~/T

OUTPUT
BREAKER

20A 240V~/T

ON

ON

INPPUT

OUTPUT ONLY CB DOES NO

T

CONNECT BYPASS POWE

R TO

MANUAL BYPASS SWIT

CH.

BREAKER 30A

ON

OFF

OFF

OFF

UPS

UTILITY

MAITANENCE BYPASS

AVAILABLE

UPS

AVAILABLE

CONNECTOR PROTECTIVE COVER DO NOT REMOVE SCREWS
PRIOR TO INSTALLATION OF BOX ON UPS
-LOOSEN THREE SCREWS 1 TURN
- SLIDE COVER TO EXPOSE CONNECTOR
-TIGHTEN SCREWS GENTLY
UPON REMOVAL OF BOX FROM UPS
-LOOSEN THREE SCREWS 1 TURN
-SLIDE COVER TO REACH END SCREW AND COVER COMMUNICATION
-TIGHTEN SCREWS GENTLY

Slide the cover over

the connectors when

the power distribution

box is removed from

the UPS.

Loosen these three

screws to move the

cover. Retighten the

screws after moving

the cover over the

connectors or off the

connectors.

These captive screws attach

the power distribution box

to the UPS

FRONT of PD-L630

power distribution

box

INSIDE FACE of PD-L630

power distribution box

Advertising