Ems input default - setback, Selecting the output type, Selecting the modulating mode default - normal – Lochinvar Harmony User Manual

Page 12: Setback, External set point (4-20ma ems-control)

Advertising
background image

12

- MODULATING MODE

>NORMAL

PARALLEL

- MODULATING MODE

NORMAL

>PARALLEL

- MODULATING MODE

NORMAL

>PARALLEL

PRESS TO SELECT

ADJUST

Press to

select

Normal

PRESS TO SELECT

ADJUST

or turn

to scroll

down

PRESS TO SELECT

ADJUST

Press to

select

Parallel

EMS INPUT

Default - Setback

Not available for Reset Sensor Types

Setback

• This default setting allows the Set Point to be adjusted either

manually at the panel, or by a Visual Gold upgrade for remote
communications.

• If desired, a dry contact switch can be wired across the EMS INPUT

terminals SIGNAL and SHIELD to allow the panel to hold a lower
temperature Set Point when less load is required. To adjust the
amount of Setback, see pg. 19.

• When selecting Setback, there is no requirement for any wiring

across the EMS INPUT terminals. DO NOT select EMS-Control
unless your system meets the requirements below.

External Set Point (4-20mA EMS-Control)

• For this option, an EMS system must provide a 4-20mA signal to

automatically change the Set Point based on pre-programmed
system parameters.

• An active signal must be wired into the EMS Harmony terminals. If

the Harmony does not receive a signal between 3.9mA and 20.1mA,
it will NOT activate any stages.

• If your system meets the above two criteria, see pg. 28 to complete

the EMS-control setup.

SELECTING THE OUTPUT TYPE

• The Harmony has two output cards, one for stages A & B, and one

for stages C & D.

• Both output cards must be programmed for the appropriate mode of

operation.

• Outputs can be configured for 4-20mA operation (current) or the

voltage range can be selected (0-5V, 0-10V, 1-5V, 2-10V).

• Check the modulating motor to determine its control requirements.
• Select the appropriate Output Type for stages A & B. The Harmony

will then automatically bring up the screen for stages C & D.

• Select the appropriate Output Type for stages C & D.
• If different types of burners are being used, stages C & D can be

selected to have a different Output Type than stages A & B.

SELECTING THE MODULATING MODE

Default - Normal

• Most boilers run more efficiently as their modulation increases.

Therefore, for most systems, it is more energy efficient to run one
boiler in high than several boilers at lower modulation. If your
system is of this type, select Normal.

• There are some systems were it may be more energy efficient to run

several units at lower modulation than one at high. If that is the case
select Parallel.

IMPORTANT: Do not select EMS-Control

unless an appropriately configured signal
from an EMS system is correctly wired into
the Harmony. For additional details, see pg.
5 for wiring, and pg. 28 for EMS-Control
setup.

PRESS TO SELECT

ADJUST

Press to

select

Setback

---- EMS INPUT ----

>Setback

EMS-Control

---- EMS INPUT ----

>Setback

EMS-Control

or turn

to scroll

down

---- EMS INPUT ----

Setback

>EMS-Control

PRESS TO SELECT

ADJUST

Press to

select

EMS

PRESS TO SELECT

ADJUST

SYSYSYSYSY
STEM STSTEM STSTEM STSTEM STSTEM ST

ARARARARAR
TUPTUPTUPTUPTUP

- OUTPUT TYPE A&B -

>4-20ma

0-10v

0-5v

- OUTPUT TYPE A&B -

4-20ma

>0-10v

0-5v

- OUTPUT TYPE A&B -

4-20ma

>0-10v

0-5v

- OUTPUT TYPE C&D -

>4-20ma

0-10v

0-5v

PRESS TO SELECT

ADJUST

Press to

select

4-20ma

PRESS TO SELECT

ADJUST

or turn

to scroll

down

PRESS TO SELECT

ADJUST

Press to

select

new

Repeat

process for

Stages C&D