Operating settings, Set pointset pointset pointset pointset point, The main display – Lochinvar Harmony User Manual

Page 14: Set point, Change set point, gain, lead stage, Set point display, Reset °f and reset °c, External set point (4-20ma ems- control)

Advertising
background image

14

OPERATING SETTINGS

CHANGE SET POINT, GAIN, LEAD STAGE

THE MAIN DISPLAY

• The main display screen may have different values in the top two

lines depending on the application.

• The third line shows the four stages. The Lead Stage will be in

brackets. For example, the Lead Stage shown at left is <A>.

• The last line shows the status of each stage. The stages may be Off

or the actual percent modulation will be displayed.

• To reach the Settings menu, press the ADJUST/SELECT knob and

release it.

SET POINT

SET POINT DISPLAY

• The Set Point is the temperature value the Harmony will use to

control the system.

• The Harmony will either increase the amount of modulation,

decrease the amount of modulation, or maintain the same amount of
modulation to maintain the system temperature around the Set Point.

• The Set Point is the target temperature the Harmony will maintain.

The system can be expected to fluctuate above and below the Set
Point. The size of the fluctuation depends on the number of stages,
the system load, and the Operating Mode selected (see pg. 13).

Outdoor Cutoff Temperature

• If the outdoor sensor is installed (see pg. 7), the Outdoor Cutoff

screen will automatically appear after the Set Point has been
selected.

• When the outdoor temperature falls to the adjustable Outdoor

Cutoff temperature, the Harmony will control and modulate stages to
hold the temperature Set Point.

• When the outdoor temperature rises to the Outdoor Cutoff tempera-

ture plus a 2°F differential, the Harmony will disable the system.

RESET °F AND RESET °C

• The Set Point is based on the Reset Ratio, Offset, and Outdoor

Cutoff. To make these settings, see pg. 25.

EXTERNAL SET POINT (4-20mA EMS- CONTROL)

• The Set Point value can only be changed by adjusting the 4-20mA

input wired into the Harmony, see pg. 28.

• Rotating the ADJUST/SELECT button will have no impact on the

Set Point value.

--- SETTINGS ---

>Set Point

Gain

Lead Stage

--- SET POINT ---

Value

--- SET POINT ---

Value -> New Value

--- SET POINT ---

Value -> New Value

Temperature

<A> B C D

OFF OFF OFF OFF

PRESS TO SELECT

ADJUST

Press to

show

Settings

PRESS TO SELECT

ADJUST

Press to

show

Set Point

PRESS TO SELECT

ADJUST

Turn to

adjust

value

PRESS TO SELECT

ADJUST

If the optional Outdoor Sensor

is installed

-- OUTDOOR CUTOFF --

Value -> New Value

-- OUTDOOR CUTOFF --

Value -> New Value

PRESS TO SELECT

ADJUST

Turn to

adjust

value

PRESS TO SELECT

ADJUST

Press to

select

new