INSTALLATION

MOUNTING THE ENCLOSURE

• Select a location near the equipment to be controlled.
• The surface should be flat, and be sufficiently wide and strong to

hold the Harmony.

• Keep the Harmony panel away from extreme heat, cold, or humidity.

Ambient operating temperature is from 20 to 120°F.

• Remove the panel from the metal enclosure by removing the top

center screw and loosening the two bottom screws. Lift the panel
out.

• Screw the enclosure to the surface through the mounting holes in

the back of the enclosure.

• Return the panel to the enclosure, replace the top screw, and tighten

the bottom two screws.

WIRING THE POWER

• Bring the 120VAC 60Hz power wires through a bottom Knockout

(KO) of the enclosure. The left front KO is preferred.

• Class 1 voltages must enter the enclosure through a different

opening from any Class 2 voltage wiring.

• Connect the hot line to terminal marked LINE.
• Connect the neutral line to the terminal marked NEUT.
• The green ground screw MUST be connected to earth ground.

INPUT WIRING

CONNECTING THE SYSTEM SENSOR

• The Harmony is designed to be connected to a

temperature sensor for immersion in a 3/8ID well.
Contact the factory for additional temperature sensor options.

• Locate the sensor in a common header where it will register the

output of all the stages in the flow and after all stages have fed the
header. If the sensor can not read the output of all the stages, it will
not be able to control the system properly.

• Temperature sensor wires can be extended up to 500’ by splicing

with 18 gauge shielded wire (Belden #8760 or equivalent).

• Do not run sensor wire in conduit with line voltage.
• Temperature sensors have no polarity. Connect the wires from the

sensor to the Harmony terminals marked TEMP- A1, A2.

• Connect the shield to the circled terminal TEMP-A2 with one of the

sensor wires.

Note: Cut the shield wire at the sensor end.

Mounting Holes

4

3

2

1

SAFETY

GROUND
MUST BE

CONNECTED

SYS

LINE

NEUTRAL

120VAC

60 Hz

Earth

Ground

To Temperature
Sensor Mounted in
Common Header

TEMP

SHUTDOWN

NETWORK

SYSTEM

PROVE

T

+

S

INPUTS

A1

A2

A3

A4

A5

A6

A7

A8

A9

A10

INSTINSTINSTINSTINST

ALLAALLAALLAALLAALLA

TIONTIONTIONTIONTION

INPUT WIRINGINPUT WIRINGINPUT WIRINGINPUT WIRINGINPUT WIRING