Reset settings, Reset ratio default 1:1, Offset default 0 – Lochinvar Harmony User Manual

Page 25

Advertising
background image

25

RESET SETTINGS

RESET RATIO

Default 1:1

• The Reset Ratio controls how much heat will be added based on

outdoor temperature. The Reset Ratios are shown as Outdoor
Temperature:Water Temperature.

• A 1:1 Reset Ratio signifies for each degree it gets colder outside, the

Calculated water temperature will raise 1 degree.

• The other Reset Ratios are adjustable from 1:4 to 4:1.
• The Reset Ratio curves start at 70°F. At 70°F the Harmony will

require 100°F water. Note that this is not the point where the
Harmony will begin giving heat. That point is determined by the
Outdoor Cutoff (next page). Also note that this starting point can be
changed by adjusting the Offset (below).

• For new installations with standard baseboard heating, begin with a

Reset Ratio of 1:1.

• For new installations with radiant heat, begin with a Reset Ratio

curve of 2:1.

• Adjust the Reset Ratio value in cold weather. If the ambient indoor

temperatures are cold in the cold weather, pick the next higher Reset
Ratio (that is, go from 1:1 to 1:1.25). If the ambient building tempera-
tures are warm in the cold weather, pick the next lower Reset Ratio
(from 1:1 to 1.25:1).

• After adjusting the Reset Ratio curve, wait at least 24 hours before

making another adjustment.

• To adjust the Reset Ratio, from the main display press the ADJUST/

SELECT knob to obtain the Settings menu. Select Set Point. The
Reset Ratio choices will now be shown.

OFFSET

Default 0

• The Offset value moves the starting point of the Reset Ratio curves

(see charts below).

• Therefore, any change made to the Offset will immediately change

the value of the Harmony Set Point water temperature by the same
amount.

• For example, if the calculated Set Point water temperature were 150°F

based on the specific outdoor temperature and Reset Ratio, then
increasing the Offset from 0°F to 10°F would increase the Set Point
water temperature to 160°F.

Outdoor Temperature (in °F)

70

60

50

40

20

30

0

-10

10

-20

Water

T

e

mper

atur

e (

in °F

)

100

120

110

130

140

150

160

180

170

190

200

210

220

1:4 1:3

1:2

1:1.5

1:1.25

1:1

1.25:1

1.5:1

2:1

3:1
4:1

RESET RATIOS

With a -20° Offset, the ratio curves

begin at 80° Water Temperature.

With a 0° Offset, the ratio curves

begin at 100° Water Temperature.

With a +20° Offset, the ratio curves

begin at 120° Water Temperature.

Outdoor Temperature

Water

Tem

per

atur

e

70

40

50

60

130

120

110

100

1:3

4:1

1:1

Outdoor Temperature

Water

Tem

per

atur

e

70

40

50

60

110

100

90

80

1:3

4:1

1:1

Outdoor Temperature

Water

Tem

per

atur

e

70

40

50

60

150

140

130

120

1:3

4:1

1:1

--- SETTINGS ---

>Set Point

Gain

Lead Stage

--- RESET RATIO ---

1.00°OD = 1.25°Sys

>1.00°OD = 1.00°Sys

1.25°OD = 1.00°Sys

--- RESET RATIO ---

1.00°OD = 1.50°Sys

>1.00°OD = 1.25°Sys

1.00°OD = 1.00°Sys

Temp

<A> B C D

OFF OFF OFF OFF

--- RESET RATIO ---

1.00°OD = 1.50°Sys

>1.00°OD = 1.25°Sys

1.00°OD = 1.00°Sys

PRESS TO SELECT

ADJUST

Press to

show

Settings

PRESS TO SELECT

ADJUST

Press to

select

Set Point

PRESS TO SELECT

ADJUST

Turn to

scroll

PRESS TO SELECT

ADJUST

Press to

select

new

RESET SETTINGSRESET SETTINGSRESET SETTINGSRESET SETTINGSRESET SETTINGS