Troubleshooting – Lochinvar Harmony User Manual

Page 27

Advertising
background image

27

TROUBLESHOOTING

No Display, or Garbled Display

Check the 120VAC power input to the Harmony. Turn power to the
Harmony off and back on.

TEMPERATURE INPUTS

Display shows OPN

Check the System Startup settings (pg. 11) to be sure the Harmony is
configured correctly to read the temperature input. Then check a
sensor is connected and the wires are continuous to the Harmony.
Finally follow the procedure for Incorrect Temperature Display.

Display shows SHT

The Harmony sees a short across the sensor input terminals.
Remove the wires from either the SYSTEM TEMP or OUT TEMP
terminals (whichever is reading SHT). The display should change to
read OPN. If it doesn’t, the Harmony may be damaged.

Display shows an Incorrect Temperature Display

Remove the wires from either the SYSTEM TEMP or OUT TEMP
terminals (whichever is reading incorrectly). The display should
change to read OPN. If it doesn’t, the Harmony may be damaged.
Take an ohm reading across the detached sensor wires. The ohm
reading should correspond to the side chart. If it doesn’t, the sensor
may be damaged.

STAGE OUTPUTS

When the unit's Mode is set to ON, the unit does not come
on

To set the Mode to ON, see pg. 22. Remove any wires attached to the
Harmony output. Check for continuity across the stage's N.O.
contacts. If there is continuity, the Harmony output is working
correctly. Check the wiring and the unit being energized to determine
why it is not operating.

Red stage light is lit, but the unit is not on

The Harmony is calling for this unit to be on. Follow the procedure above.

Red stage light is not lit, but the unit is on

The Harmony is not calling for this unit to be active. Remove any wires attached to the Harmony output. Check for
continuity across the N.O. contacts. If there is no continuity, the Harmony output is working correctly. Check the unit
for any other operating controls which may be causing it to energize.

SYSTEM OUTPUT

Output is required but the SYSTEM component does not come on

Check the display to see if the temperature is above the Set Point or if the Outdoor Cutoff is active.

Red SYSTEM light is lit, but the SYSTEM component is not on

The Harmony is calling for the unit. Check for continuity across the N.O. SYS contacts. If there is continuity, the
Harmony is working correctly. Check the wiring and the component being energized to determine why it is not
operating.

Red stage light is not lit, but the SYSTEM component is on

The Harmony is not calling for the component to run. Remove any wires attached to the Harmony's SYS terminals.
Check the N.O. terminals are open. If they are, check the unit for any other operating controls which may be causing it
to energize.

0

42683

10

31215

20

23089

25

19939

30

17264

35

14985

40

13040

45

11374

50

9944

55

8714

60

7653

70

5941

80

4649

90

3667

100

2914

110

2332

120

1879

130

1524

140

1243

150

1021

160

842

170

699

180

583

190

489

200

412

TEMPERATURE

(in degrees F)

Value

(in Ohms)

TRTRTRTRTR
OUBLESHOOOUBLESHOOOUBLESHOOOUBLESHOOOUBLESHOO

TINGTINGTINGTINGTING