Ab c d, Wiring to 4-20 ma modulating motors, Wiring to voltage modulating motors – Lochinvar Harmony User Manual

Page 9: Wiring the stage outputs, 20 ma modulation outputs, Voltage

Advertising
background image

9

Wiring the Stage Outputs

• Each Stage output (A through D) has one Normally Open (N.O.)

relay contact.

• The N.O. contacts are dry contacts only. They do not source any

voltage.

• Each N.O. contact is capable of switching 6A resistive at 120VAC.
• Total output of all stages, including the SYS, must not exceed 15A.
• Wire the N.O. relay contacts in series with the boiler’s limit circuit.
• Class 1 voltages must enter the enclosure through a different

opening from any Class 2 voltage wiring.

WIRING TO 4-20 MA MODULATING MOTORS

• The Harmony can be equipped to operate up to four 4-20 mA

modulating motors.

• To program the control for 4-20 mA output, see System Startup

settings, pg. 12.

• Apply the supplied label marked 4-20 mA below the output termi-

nals.

• The output boards are connected on the rear of the panel.
• The pair of outputs A and B are controlled by a one output board.

The pair of outputs C and D are controlled by a second output
board.

• The Harmony sources 24VDC excitation voltage for the 4-20mA

signal.

• Wire as shown below:

mA Source (+)

Common

Stage A

Stage B

Stage C

Stage D

C1

C4

C7

C10

C2

C5

C8

C11

Harmony

Sources

Current

WIRING TO VOLTAGE MODULATING MOTORS

• The Harmony can be equipped to operate up to four 0-5 V, 0-10V, 1-

5V, or 2-10V modulating motors.

• Apply the supplied label marked Voltage below the output terminals.
• The output boards are connected on the rear of the panel.
• To select the range, 0-5V, 0-10V, 1-5V or 1-10V, see pg. 12.
• The pair of outputs A and B are controlled by a one output board.

The pair of outputs C and D are controlled by another output board.

• Wire as shown below:

V+

GND

Stage A

Stage B

Stage C

Stage D

C1

C4

C7

C10

C3

C6

C9

C12

INSTINSTINSTINSTINST

ALLAALLAALLAALLAALLA

TIONTIONTIONTIONTION

OUTPUT WIRINGOUTPUT WIRINGOUTPUT WIRINGOUTPUT WIRINGOUTPUT WIRING

10

9

8

7

6

5

4

3

11

12

SYS

A

B

C

D

OPERATING LIMIT

OUTPUTS

C

Limit Circuit

Typical for each stage

4-20 mA

MODULATION OUTPUTS

A

mA

B

C

D

C1

C2

C3

C4

C5

C6

C7

C8

C9 C10 C11 C12

4 - 20mA

Motor

- +

Common

mA

Common

mA

Common

mA

Common

A

0- 5 V

or

0-10V

Motor

GND

V+

B

0- 5 V

or

0-10V

Motor

GND

V+

C

0- 5 V

or

0-10V

Motor

GND

V+

D

0- 5 V

or

0-10V

Motor

GND

V+

C1

C2

C3

C4

C5

C6

C7

C8

C9 C10 C11 C12

MODULATION OUTPUTS

Voltage

A

B

C

D

Advertising