GAIN/THROTTLE

OPERATING MODE - NORMAL

Default = 0

• The Gain adjusts the PID logic in the Harmony to control how much

modulation is changed when the system temperature is different
from the Set Point.

• A Gain of 0 is a good starting point for all systems.
• If, during normal load conditions, the system temperature tends to

fluctuate significantly above and below the Set Point, decrease the
Gain by two numbers (for example, from 0 to -2). Wait for at least 15
minutes before evaluating how the change has affected the system.

• If, during normal load conditions the system temperature tends to

remain consistently below the Set Point (or consistently above the
Set Point), increase the Gain by two numbers (for example, from 0 to
2). Wait for at least 15 minutes before evaluating how the change has
affected the system.

OPERATING MODE - PROCESS Default = 1.0

• The Gain acts as a throttling range around the Set Point.
• When the actual temperature is equal to the Set Point, the lead stage

will be at 100% modulation.

• Each throttling range above or below the Set Point controls one

stages modulation linearly from 0 to 100%.

• The Process Gain Table below shows the relationship between the

Gain and stage modulation.

• The Process Gain Table does not show all the possible modulation

values. The table is for example only. The Harmony will control the
modulation in one percent increments based on the Set Point and
Gain value.

--- SETTINGS ---

Set Point

>Gain

Lead Stage

--- GAIN ---

Value -> New Value

--- GAIN ---

Value -> New Value

PRESS TO SELECT

ADJUST

Press to

show

setting

PRESS TO SELECT

ADJUST

Turn to

adjust

value

PRESS TO SELECT

ADJUST

Press to

select

new

PROCESS GAIN/THROTTLING RANGE TABLE

GAIN - GAIN - GAIN - GAIN - GAIN -

THRTHRTHRTHRTHR

OOOOO

TTLETTLETTLETTLETTLE

1 x Gain Above Set Point

Lead Stage at 0%

At Set Point

Lead Stage at 100%

0.5 x Gain Below Set Point

Lead Stage at 100%, 1 Lag at 50%

1x Gain Below Set Point

Lead and 1 Lag at 100%

2 x Gain Below Set Point

Lead and 2 Lag at 100%

3 x Gain Below Set Point

All Stages at 100%

2 x Gain Above Set Point

Lead Stage at 0%

2.5 x Gain Setting Above Set Point

All Stages OFF

0.5 x Gain AboveSet Point

Lead Stage at 50%

SYSTEM TEMPERATURE

STAGES MODULATION

3 x Gain Setting Above Set Point

All Stages OFF

2.5 x Gain Below Set Point

Lead and 2 Lag at 100%