N.O. contacts to activate a pump,
valve or other system component

WIRING THE SYSTEM OUTPUT

System Output Operation in Set Point Mode

• The SYS output relay will energize whenever there is a call for output

and the Shutdown feature is not active.

• Until the SYSTEM PROVE input is shorted, no Stages will be

activated. If a Prove is not required, the factory installed jumper
should remain.

• The SYS will remain energized while any Stage is active.
• When the last Stage relay turns off, the SYS output can remain

energized for the period of time set by the System Run-On (see pg.
19)

• A typical use of the SYS output is to activate a system pump starter.

The pump can run whenever there is a call for heat. When heat is no
longer required, the pump will stay active for a few more minutes to
remove the residual heat from the boilers.

System Output Operation in Reset Mode

• The SYS output relay will energize whenever the outdoor tempera-

ture is below the Outdoor Cutoff.

• The SYS will remain constantly energized while the outdoor tempera-

ture is below the Outdoor Cutoff.

• When the outdoor temperature rises 2°F above the Outdoor Cutoff,

the SYS output will remain energized for the period of time set by the
System Run-On (see pg. 19).

Wiring the SYS Output

• The SYS output has one Normally Open (N.O.) relay contact.
• The N.O. contacts are dry contacts only. They do not source any

voltage.

• Class 1 voltages must enter the enclosure through a different

opening from any Class 2 voltage wiring.

• Each N.O. contact is capable of switching 6A resistive at 120VAC.
• Total output SYS and the OPERATING LIMIT OUTPUTS must not

exceed 15A.

WIRING THE STAGE OUTPUTS

Installing the Output Relays

• Each output stage (A through D) which is to be used must have a

relay installed in the socket.
The SYS relay is included with the Harmony.

• To install a relay, orient the pins and then press it gently into the

appropriate socket.

• Any stage output which does not have a relay must have its Mode

set to Off (see Stage Settings pg. 22).

INSTINSTINSTINSTINST

ALLAALLAALLAALLAALLA

TIONTIONTIONTIONTION

OUTPUT WIRINGOUTPUT WIRINGOUTPUT WIRINGOUTPUT WIRINGOUTPUT WIRING