Harmony function chart, Harmony, Full modulation sequencing control – Lochinvar Harmony User Manual

Page 2: Ab c d

Advertising
background image

2

Harmony Function Chart

Green Ground
screw must be
connected to
Earth Ground

120VAC

Power

System Output
controls pumps,
valves or other system
components

Each N.O. output is
wired in series with
each unit's limit circuit

The modulation outputs can be 0-5V, 0-10V,
1-5V, 2-10V, or 4-20ma

. Different output

boards mount on the back of the Harmony
and determine the type of output.

One output relay is required for

each stage.

If input is not made,
the Harmony will not
consider it an active
stage*

To Temp sensor mounted
in common header

When closed, all stages
are turned off*

* DRY CONTACTS ONLY
** Only available with the Remote Communications package

Checks status of system
components*

Depress the knob to move
forward through the menus and to
accept changes, rotate the knob
to change a setting's value

Depress the button to go back
through the menus, or to view a
setting value without changing it

The digital display shows the system status,
set point, lead stage <in brackets>, and
status of each stage. To view and adjust
settings, press the Adjust/Select button

FULL MODULATION

SEQUENCING CONTROL

HARMONY

MADE IN U.S.A.

PREV.

10

9

8

7

6

5

4

3

2

1

11

12

SAFETY

GROUND
MUST BE

CONNECTED

SYS

SYSTEM

TEMP

SHUTDOWN

SYSTEM

PROVE

MENU FUNCTIONS

SELECT enters menus or accepts changes

ADJUST selects menu items or changes settings

BACK returns to previous menu

STAGE selects stage menus or next stage

PREV/NEXT steps through stage settings

STAGE

A

STAGE

B

STAGE

C

STAGE

D

SYSTEM

A

B

C

D

LI

N

E

NE

UT

RAL

A

B

C

D

OPERATING LIMIT

OUTPUTS

MODULATION OUTPUTS

STAGE

HELP

NEXT

PRESS TO

SELECT

BACK

181

<A>

B

C

D

100

52

OFF

STBY

A

B

C

D

C

C1

C2

C3

C4

C5

C6

C7

C8

C9

C10 C11 C12

ADJUST

T

+

S

INPUTS

A1

A2

A3

A4

A5

A6

A7

A8

A9

A10

BURNER

ACTIVE

B1

B2

B3

B4

B5

B6

B7

B8

A11

A12

OUTDOOR

TEMP

T

Optional sensor enables
outdoor reset

DO NOT APPLY ANY VOLTAGE

TO SENSOR TERMINALS

EMS INPUT

+

SIGNAL

SHIELD

Provides remote set
point adjustment with
a 4-20mA signal

To network sensors**

NETWORK