Configuring Modbus

Modbus Serial Port Settings

Modbus Master Settings

When the Modbus Masters is attached to the IOLAN’s serial port, configure that serial port to the

Modbus Gateway

profile acting as a Modbus Master. You must configure the Modbus TCP Slaves

on the TCP/Ethernet side so the IOLAN can properly route messages, using the Modbus Slave’s
UIDs, to the appropriate TCP-attached devices.

To configure the Modbus Master on serial port 1, do the following:

1.

Select the

Modbus Gateway

profile for serial port 1.

2.

On the

General

tab, enable the

Modbus Master

parameter.

3.

Click the

Destination Slave IP Mappings

button and click the

Add

button in the Destination

Slave IP Mappings window.

4.

Configure the Destination Slave IP Mappings window as follows:

The IOLAN will send a request and expect a response from the Modbus Slave with an IP
Address of 10.10.10.11 on Port 502 with UID 22 and from the Modbus Slave with and IP
Address of 10.10.10.12 on Port 502 with UID 23 (remember when

Type

is set to

Host

, the

IOLAN increments the last octet of the IP address for each UID specified in the range).

EIA-422/485

Network

EIA-232

TCP

Modbus Master

Master Gateway

Modbus Master

Serial

Modbus Slave

IP: 10.10.10.11

UID: 22

Modbus Slave

IP: 10.10.10.12

UID: 23

IOLAN

IP: 10.10.10.10