Temperature input, Thermocouple rtd 2-wire rtd 3-wire – Perle Systems IOLAN SCS User Manual

Page 372

Advertising
background image

Wiring I/O Diagrams

372

IOLAN SDS/SCS/STS User’s Guide, Version 3.6

Temperature Input

If you are using RTD sensors, a short detected status will be displayed if the wires are connected
improperly. RTD or thermocouple sensors will display an open detection status when the circuit is
broken.

Thermocouple

To connect to Channel A1 with a 2-wire cable, connect the positive wire to A1+ and the negative
wire to A1-; you will not be using the A1s connection.

RTD 2-Wire

In a 2-wire RTD configuration, connect the excite wire to A1-, the return wire to A1+, and jumper the
sense wire from A1s with a insulated wire going to A1+.

RTD 3-Wire

In a 3-wire RTD configuration, connect the return wire to A1+, the excite wire to A1-, and the sense
wire to A1s.

A1+

A1-

A1s

A2s

A2+

A2-

A3

+

A3

-

A3

s

A4

s

A4

+

A4

-

+

-

A1+

A1-

A1s

A2s

A2+

A2-

A3

+

A3

-

A3

s

A4

s

A4

+

A4

-

return

excite

sense

A1

+

A1

-

A1

s

A2

s

A2

+

A2

-

A3+

A3-

A3s

A4s

A4+

A4-

return

excite

sense