DC rack cabling

37

Length

#10 AWG

#8 AWG

#6 AWG

Junction
box #4
AWG

Junction
box #4
AWG

0-210 m (700 ft)

no

no

no

no

yes

Over 210 m (700 ft)

no

no

no

no

no

Notes:

1.

The cabinet and module ground wire specification is #10 AWG insulated green safety ground wire.

2.

The cabinet conduit can be 19.1 mm (0.75-in.) or 31.8 mm (1.25-in.), and must be insulated
from the cabinet ground.

Metric wire conversion

AWG No.

Industry standard
nominal (sq mm)

Resistance at 20 C
(Ohm/100 m)

2

35

0.05

4

25

0.08

6

16

0.13

8

10

0.20

10

6

0.33

12

4

0.63

14

2.5

1.00

16

1.5

1.40

18

1

2.00

20

0.75

2.90

22

0.5

4.60