Chapter 4 Power supply installation

the same service panel as CallPilot and the switch, whether or not the
equipment is AC- or DC-powered.

-48 V DC power distribution rationale

Minimum installation is one power distribution unit (PDU) with four 48 V
DC branch circuits fused at 20 amperes.

The customer must be able to shut off any branch to ensure every unit
at the site continues to function properly.

DC-powered configuration fits into this scheme as follows:

— Each PDU receives four branch circuits.

— Each server receives a feed from each PDU and a different branch

circuit.

In this fashion, with dual hot-swappable power supplies, there is no
single point of failure in the power system. For example, you can remove
any power supply, including a PDU, and everything continues to work.

This is applicable to either North American or European installation
sites (with a 230 V AC inverter).

The secondary rack supports four servers and follows a similar scheme.

About the power distribution unit

Introduction

A PDU is installed in a rack that has DC-powered servers. Power from
the DC supply source enters the PDU and can then be distributed to one
or more servers. A single PDU can supply DC power to four DC power
supply modules. A server can have either one or two power supply modules
installed. You can determine the number of PDUs to install in a rack by
counting the number of power supply modules in each rack.

PDU power and grounding

To ensure a complete power and grounding installation:

In rackmount DC-powered server installations, ensure the PDU (Power
Distribution Unit for DC applications) is installed on the same rack as
the CallPilot server. This is required since the main ground wire for the
PDU is not insulated from the metal enclosure.

Multiple PDUs

A server operates on a single power supply module. Its total capacity is
two installed power supply modules. The second power supply module is
the redundant power supply module.