Nortel Networks Server 1005r User Manual

Page 43

Advertising
background image

Connecting the server to power

43

Provide a sufficient number of properly grounded power outlets or power
bars for all equipment. For more information, refer to grounding and power
requirements in this document and in the Planning and Engineering Guide
(NN44200-200).

The single-point ground (SPG) required by the system can be an isolated
ground (IG) bus or AC equipment ground (ACEG) bus in the service panel or
transformer. The system must be connected to safety ground or protective
earth in accordance with NEC requirements. For international use, the
system must be connected to safety ground/protective earth in accordance
with Paragraph 2.5 of EN60950/IEC950.

Note: See Large System: Planning and Engineering (553-3021-120)
for a complete description of approved ground sources and methods.
Insulated ground wire must be used for system grounding.

Before you connect the server to the power source, review the following
diagram to ensure that all peripheral hardware devices are in place.

1005r server in a network.

Nortel CallPilot

1005r Server Hardware Installation

NN44200-308

01.06

Standard

5.0

15 May 2008

Copyright © 2006-2008, Nortel Networks

.