Bgd36cf(g) top exit / horizontal termination, 90° h – Napoleon Fireplaces BGD36CFPTR User Manual

Page 12

Advertising
background image

12

W415-0661 / C / 02.20.08

For vent confi gurations requiring more than one 90° elbow the fol-
lowing formulas apply:

Formula 1: H

T

< 4.2 V

T

Formula 2: H

T

+ V

T

< 24.75 feet

Example 2:

See graph to determine the required vertical
rise V

T

for the required horizontal run H

T

.

V

1

=V

T

= 6 ft

H

1

=3 ft

H

2

=5 ft

H

R

=H

1

+ H

2

= 3 + 5 = 8 ft

H

O

=.03 (two 90° elbows - 90°) = .03(180° - 90°) = 2.7 ft

H

T

=H

R

+ H

O

= 8 + 2.7 = 10.7 ft

H

T

+ V

T

= 10.7 + 6 =16.7

Formula 1: H

T

< 4.2 V

T

4.2 V

T

= 4.2 x 6 = 25.2 ft

10.7 < 25.2

Formula 2: H

T

+ V

T

< 24.75 feet

16.7

<

24.75

Since both formulas are met, this vent confi guration is acceptable.

REQUIRED VERTICAL RISE

IN INCHES V

T

HORIZONTAL VENT

RUN PLUS OFFSET IN

FEET H

T

The shaded area within the lines represents acceptable values
for H

T

and V

T

.

when (H

T

) > (V

T

)

Simple venting confi guration (only one 90°
elbow)

BGD36CF(G) TOP EXIT / HORIZONTAL TERMINATION

H

2

H

1

V

1

90°

FIGURE 23

H

2

H

4

V

2

90°

H

3

H

1

V

1

90°

FIGURE 24

FIGURE 22

Example 3:

V

1

= 4 ft

V

2

= 1.5 ft

V

T

= V

1

+ V

2

= 4 + 1.5 = 5.5 ft

H

1

= 2 ft

H

2

= 1 ft

H

3

= 1 ft

H

4

= 1.5 ft

H

R

= H

1

+ H

2

+ H

3

+ H

4

= 2 + 1 + 1 + 1. 5 = 5.5 ft

H

O

= .03 (four 90° elbows - 90°) = .03(360° - 90°) = 8.1 ft

H

T

= H

R

+ H

O

= 5.5 + 8.1 = 13.6 ft

H

T

+ V

T

= 13.6 + 5.5 = 19.1 ft

Formula 1:

H

T

< 4.2 V

T

4.2

V

T

= 4.2 x 5.5 = 23.1 ft

13.6 < 23.1

Formula 2:

H

T

+ V

T

< 24.75 feet

19.1

<

24.75

Since both formulas are met, this vent confi guration is ac-
ceptable.