Bgd36cf(g) rear exit / horizontal termination, 90° h – Napoleon Fireplaces BGD36CFPTR User Manual

Page 13

Advertising
background image

13

W415-0661 / C / 02.20.08

See graph to determine the required vertical rise V

T

for the required

horizontal run H

T

For vent confi gurations requiring more than two 90° elbows the fol-
lowing formulas apply:

Formula 1: H

T

< V

T

REQUIRED VER-
TICAL RISE IN
FEET

V

T

HORIZONTAL VENT RUN PLUS OFF-

SETS IN FEET H

T

Formula 2: H

T

+ V

T

< 40 feet

Example 4:

V

1

= 9 ft

V

2

= 6 ft

V

T

= V

1

+ V

2

= 9 + 6 = 15 ft

H

1

= 3 ft

H

2

= 2 ft

H

3

= 1.5 ft

H

R

= H

1

+ H

2

+ H

3

= 3 + 2 + 1.5 = 6.5 ft

H

O

= .03 (four 90° elbows - 90°)

= .03(90 + 90 + 90 + 90 - 90) = 8.1 ft

H

T

= H

R

+ H

O

= 6.5 + 8.1 = 14.6 ft

H

T

+ V

T

= 14.6 + 15 = 29.6 ft

Formula 1:

H

T

< V

T

14.6 < 15

Formula 2:

H

T

+ V

T

< 40 feet

29.6

<

40

Since both formulas are met, this vent confi guration is ac-
ceptable.

The shaded area within the lines represents acceptable values
for H

T

and V

T

.

BGD36CF(G) REAR EXIT / HORIZONTAL TERMINATION

when (H

T

) < (V

T

)

Simple venting confi guration (only two 90° elbows)

FIGURE 25

H

2

V

1

V

2

H

3

90°

90°

90°

90°

H

1

FIGURE 26

Example 5:

V

1

=4 ft

V

2

=1.5 ft

V

T

=V

1

+ V

2

= 4 + 1.5 = 5.5 ft

H

1

=2 ft

H

2

=1 ft

H

3

=1 ft

H

4

=1.5 ft

H

R

=H

1

+ H

2

+ H

3

+ H

4

= 2 + 1 + 1 + 1.5 = 5.5 ft

H

O

=.03 (four 90° elbows + one 45° elbow - 90°)

=.03(90 + 90 + 90 + 90 + 45 - 90) = 9.45 ft

H

T

=H

R

+ H

O

= 5.5 + 9.45 = 14.95 ft

H

T

+ V

T

= 14.95 + 5.5 = 20.45 ft

Formula 1:

H

T

< 3.5V

T

3.5V

T

= 3.5 x 5.5 = 19.25 ft

14.95 < 19.25

Formula 2:

H

T

+ V

T

< 24.75 feet

20.45

<

24.75

Since both formulas are met, this vent confi guration is ac-
ceptable.

For vent confi gurations requiring more than two 90° elbows the fol-
lowing formulas apply:

Formula 1: H

T

< 3.5V

T

Formula 2: H

T

+ V

T

< 24.75 feet

REQUIRED VERTICAL
RISE IN INCHES

HORIZONTAL VENT RUN

PLUS OFFSETS IN FEET H

T

See graph to determine the required vertical rise V

T

for the required

horizontal run H

T

V

T

The shaded area within the lines represents acceptable
values for H

T

and V

T

.

FIGURE 27

H

1

H

2

H

3

H

4

V

1

V

2

90°

90°

45°

90°

90°

FIGURE 28

when (H

T

) > (V

T

)

Simple venting
confi guration (only
two 90° elbows)

Advertising